Info | ||
---|---|---|
| ||
<WorkspaceDirectory>\ConfigFiles\xio.OPCUA.cfg |
Parameter | Description | Scope | Unit | Default value |
---|---|---|---|---|
xio.OPCUA.Enabled | Enables/disables the OPC UA server interface. | true/false | none | false |
xio.OPCUA.LocalTCPPort | Port of the local OPC UA TCP transport binding. | 1 - 65535 | TCP port | 48400 |
xio.OPCUA.LocalHTTPPort | Port of the local OPC UA http transport binding. | 1 - 65535 | TCP port | 48401 |
xio.OPCUA.UseBmsAuthentication | Only available for BMS Platform: If enabled, the BMS user authentication module is also used for OPC UA | true/false | none | true |
xio.OPCUA.Username | If BMS authentication is not |
enabled or NETx MP Server is used, the user for connecting to OPC UA has to be specified here. As an alternative, anonymous access can be enabled. | string | none | none |
xio.OPCUA.Password | If BMS authentication is not |
enabled or NETx MP Server is used, the password for connecting to OPC UA has to be specified here. As an alternative, anonymous access can be enabled. | string | none | none | |
xio.OPCUA.AnonAccess | If enabled, no user name / password has to be specified for connecting to OPC UA (not recommended). | true/false | none | false |
xio.OPCUA.ApplicationCertificateLifeTime | Certificate lifetime (in months) for newly created certificates. | 1 - 65535 | months | 120 |
xio.OPCUA.ApplicationCertificatePath | Path to the application certificate within the Windows certificate store. | LocalMachine\NETx BMS Platform | ||
xio.OPCUA.ApplicationCertificateSubjectName | Subject name of application certificate. | NETx BMS Platform UA Wrapper | ||
xio.OPCUA.TrustedPeerCertificatesPath | Path to trusted peer certificates within the Windows certificate store. | LocalMachine\NETx BMS Platform | ||
xio.OPCUA.TrustedIssuerCertificatesPath | Path to trusted issuer certificates within the Windows certificate store. | LocalMachine\NETx BMS Platform |