Manufacturer | Type | Emergency | Fault General | Fault DALI | Fault Lamps | Fault Ballast | Fault Converter | Error Status Lamp/Ballast | Emergency Start | Emergency Result |
---|---|---|---|---|---|---|---|---|---|---|
Ipas | DaliControl e64 (plugin version) | yes | #8 | #9 | #12 | #14 | #16 | #20 | #176, offset: 11 | #177, offset: 11 |
DaliControl e64 | yes | #13 | #14 | #17 | #19 | #21 | #29 | #490, offset: 13 | #491, offset: 13 | |
DaliControl gc16 | no | #10 | #11 | #14 | #16 | NA | #20 | NA | NA | |
DaliControl gc16-2 | no | #12, #652 | #13, #653 | #16, #656 | #18, #658 | NA | #22, #662 | NA | NA | |
Merten | DALI gateway REG-K/1/16(64)/64/IP1 (plugin version) | yes | #8 | #9 | #12 | #14 | #16 | #20 | #176, offset: 11 | #177, offset: 11 |
DALI gateway REG-K/1/16(64)/64/IP1 | yes | #13 | #14 | #17 | #19 | #21 | #29 | #490, offset: 13 | #491, offset: 13 | |
DALI-Gateway Basic REG-K/1/16/64 | no | #10 | #11 | #14 | #16 | NA | #20 | NA | NA | |
DALI Gateway Basic REG-K/2/16/64 | no | #12, #652 | #13, #653 | #16, #656 | #18, #658 | NA | #22, #662 | NA | NA | |
Schneider | DALI gateway REG-K/1/16(64)/64/IP1 (plugin version) | yes | #8 | #9 | #12 | #14 | #16 | #20 | #176, offset: 11 | #177, offset: 11 |
DALI gateway REG-K/1/16(64)/64/IP1 | yes | #13 | #14 | #17 | #19 | #21 | #29 | #490, offset: 13 | #491, offset: 13 | |
DALI-Gateway Basic REG-K/1/16/64 | no | #10 | #11 | #14 | #16 | NA | #20 | NA | NA | |
DALI Gateway Basic REG-K/2/16/64 | no | #12, #652 | #13, #653 | #16, #656 | #18, #658 | NA | #22, #662 | NA | NA | |
MDT | Dali Control IP 64 (plugin version) | yes | #8 | #9 | #12 | #14 | #16 | #20 | #176, offset: 11 | #177, offset: 11 |
Dali Control IP 64 | yes | #13 | #14 | #17 | #19 | #21 | #29 | #490, offset: 13 | #491, offset: 13 | |
Dali Control 32 | no | #12, #652 | #13, #653 | #16, #656 | #18, #658 | NA | #22, #662 | NA | NA | |
Dali Control 16 | no | #10 | #11 | #14 | #16 | NA | #20 | NA | NA | |
B.E.G. | DALI/KNX Gateway IP-N | yes | #8 | #9 | #12 | #14 | #16 | #20 | #176, offset: 11 | #177, offset: 11 |
Theben | DALI-Gateway KNX plus (plugin version) | yes | #8 | #9 | #12 | #14 | #16 | #20 | #176, offset: 11 | #177, offset: 11 |
DALI-Gateway KNX plus | yes | #13 | #14 | #17 | #19 | #21 | #29 | #490, offset: 13 | #491, offset: 13 | |
DALI-Gateway S64 KNX | no | #10 | #11 | #14 | #16 | NA | #20 | NA | NA | |
DALI-Gateway S128 KNX | no | #12, #652 | #13, #653 | #16, #656 | #18, #658 | NA | #22, #662 | NA | NA |
...
Since these gateways do not have a global KNX communication object for starting an emergency test and for getting the result (they have a separate object for each device), the ItemIDs has to be configured for each emergency lighting separately. This is done in the Emergency Test MappingIpas DaliControl, MDT DaliControl, Merten KNX DALI-Gateway, Schneider KNX DALI-Gateway, B.E.G. DALI/KNX-Gateway, Theben DALI-Gateway KNX.
Functional description
These KNX/DALI gateway types provide 1 DALI channel with up to 64 DALI devices. In addition to normal DALI testing, they support emergency lighting and extended tests for emergency lighting too.
...
Include Page | ||||
---|---|---|---|---|
|
For emergency DALI testing, the following Server Items are available under the sub tree "Emergency":
...
item name | description | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Test Running | True, when an emergency DALI test is currently running. | ||||||||||||||
Start Function Test | Used to trigger a function test for this device. | ||||||||||||||
Start Duration Test | Used to trigger a duration test for this device. | ||||||||||||||
Start Battery Test | Used to trigger a battery test for this device. | ||||||||||||||
Stop Test | Used to stop a running test. | ||||||||||||||
Last test was | Shows the type of the last test.
| ||||||||||||||
Last test faulted | True, if there was no test result response. This may be the case when the DALI does not support emergency tests. | ||||||||||||||
Converter defect | True, if the converter is defect. | ||||||||||||||
Fault battery | True, if there is a battery fault. | ||||||||||||||
Battery defect | True, if the battery is defect. | ||||||||||||||
Fault emergency light | True, if there is an emergency light failure. | ||||||||||||||
Max time function test exceeded | True, if the maximum time for the function test exceeded. | ||||||||||||||
Max time duration test exceeded | True, if the maximum time for the duration test exceeded. | ||||||||||||||
Function test failed | True, if the function test failed. | ||||||||||||||
Duration test failed | True, if the duration test failed. | ||||||||||||||
Test result | Test result: The raw data as received from the gateway. Time results have to be multiplied by 2 minutes; Battery charge status is from 0 to 255 and has to be converted to percentage. |
Include Page | ||||
---|---|---|---|---|
|