Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.
Info

Access: Core Studio > Modules > LaMPS > DALI > UPS definitions

Info

File location: <WorkspaceDirectory>\DataFiles\xio.LaMPS.UpsDefinitinos.dat

Each row in the table specifies a UPS device.

Col#

Parameter

Description

Scope

Unit

Default value

1

Name

UPS name

String

None

2

Path

Path inside NETx\Module\LaMPS\UPS

String

None

empty

3

Battery level

Data point that holds the charge level of the UPS battery in percent.

ItemID

None

empty

4

Battery level threshold

Data point that holds the battery charge threshold. Levels below the threshold lead UPS tests to be considered as failed.

ItemID

None

empty

5

Battery level manual override

If enabled, a manual override of the battery charge level device reading is written to the database.

Boolean

None

False

6

Function test duration

Duration of the UPS function test.

Numeric

min

10

7

Partial duration test duration

Duration of the UPS partail duration test.

Numeric

min

240

8

Test start delay

Interval that is awaited after a test was triggered and before the test is started.

Numeric

s

10

...