Configuration

...

Warning
The group object "Emergency Test Start" (#58 or #1520 / #2080) has to be configured for "Yes, DGN/S1.16.1 format" within ETS. Otherwise the emergency lighting tests will not work.

Info

The ABB DG/S x.64.5.1 gateway uses emergency test start and result objects for all devices on one channel – there are no individual objects for each emergency ballast as it is for other gateways. Therefore, there will appear no entry within the Emergency Mapping Definitions. If the emergency configuration is enabled it will appear within the ABB DG/S x.64.5.1 gateway definition.

Functional description

These KNX/DALI gateway types provide 1 or 2 DALI channels with up to 64 DALI devices. In addition to normal DALI testing, they support emergency lighting and extended tests for emergency lighting too.

...