The configuration of the main/backup functionality is done in the Main/Backup configuration file.

Info
title

File location

<WorkspaceDirectory>\ConfigFiles\nxaXLink.40.cfg

Parameter

Description

Scope

Unit

Default value

XLINK.Redundancy

If ON, the main/backup functionality will be activated.

ON, OFF

None

OFF

XLINK.MainServerIPAddress

The IP address of the main server's network interface.

IP address

None

None

XLINK.BackupServerIPAddress

The IP address of the backup server's network interface.

IP address

None

None

XLINK.MainServerPort

TCP port for secure connection to main server

1 – 65535

None

14732

XLINK.Password

TLS connection password for second server

String

None

None

XLINK.PIN

TLS connection PIN of this server.

String

None

None

XLINK.ConnectionTimeout

Specifies the timeout for a detecting a lost connection to the second server. If the second server does not response within the given time interval, it will assume that the second server is down.

1 – 600

s

10

XLINK.CommandTimeout

Specifies the timeout in seconds of VNET commands between main and backup server.

1 – 10000

s

30

Article applies to the following products:

  • NETx BMS Platform

  • NETx Multi Protocol Server

...