Since these gateways do not have a global KNX communication object for starting an emergency test and for getting the result (they have a separate object for each device), the ItemIDs has to be configured for each emergency lighting separately. This is done in the Ipas DaliControl, MDT DaliControl, Merten KNX DALI-Gateway, Schneider KNX DALI-Gateway, B.E.G. DALI/KNX-Gateway, Theben DALI-Gateway KNXKNX#EmergencyTestMapping.
Functional description
These KNX/DALI gateway types provide 1 DALI channel with up to 64 DALI devices. In addition to normal DALI testing, they support emergency lighting and extended tests for emergency lighting too.
...
item name | description | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Test Running | True, when an emergency DALI test is currently running. | ||||||||||||||
Start Function Test | Used to trigger a function test for this device. | ||||||||||||||
Start Duration Test | Used to trigger a duration test for this device. | ||||||||||||||
Start Battery Test | Used to trigger a battery test for this device. | ||||||||||||||
Stop Test | Used to stop a running test. | ||||||||||||||
Remaining Test Runtime | Remaining runtime in minutes for a triggered test. | ||||||||||||||
Last test was | Shows the type of the last test.
| ||||||||||||||
Last test faulted | True, if there was no test result response. This may be the case when the DALI does not support emergency tests. | ||||||||||||||
Converter defect | True, if the converter is defect. | ||||||||||||||
Fault battery | True, if there is a battery fault. | ||||||||||||||
Battery defect | True, if the battery is defect. | ||||||||||||||
Fault emergency light | True, if there is an emergency light failure. | ||||||||||||||
Max time function test exceeded | True, if the maximum time for the function test exceeded. | ||||||||||||||
Max time duration test exceeded | True, if the maximum time for the duration test exceeded. | ||||||||||||||
Function test failed | True, if the function test failed. | ||||||||||||||
Duration test failed | True, if the duration test failed. | ||||||||||||||
Test result | Test result: The raw data as received from the gateway. Time results have to be multiplied by 2 minutes; Battery charge status is from 0 to 255 and has to be converted to percentage. |
...