Configuration

...

Warning
The group object "Emergency Test Start" (#58 or #1520 / #2080) has to be configured for "Yes, DGN/S1.16.1 format" within ETS. Otherwise the emergency lighting tests will not work.

Info

The ABB DG/S x.64.5.1 gateway uses emergency test start and result objects for all devices on one channel – there are no individual objects for each emergency ballast as it is for other gateways. Therefore, there will appear no entry within the Emergency Mapping Definitions. If the emergency configuration is enabled it will appear within the ABB DG/S x.64.5.1 gateway definition.

Functional description

These KNX/DALI gateway types provide 1 or 2 DALI channels with up to 64 DALI devices. In addition to normal DALI testing, they support emergency lighting and extended tests for emergency lighting too.

...

item name

description

Test RunningTrue, when an emergency DALI test is currently running.
Start Function TestUsed to trigger a function test for this device.
Start Duration TestUsed to trigger a duration test for this device.
Start Partial Duration TestUsed to trigger a partial duration test for this device.
Start Battery TestUsed to trigger a battery test for this device.
Stop TestUsed to stop a running test.
Remaining Test Runtime

Remaining runtime in minutes for a triggered test.

Last test was

Shows the type of the last test. 

value

description

0"No Test"
1"Function Test"
2"Partial duration test"
3"Duration test"
4"Battery test"
255"Test not supported"


Last test faultedTrue, if there was no test result response. This may be the case if the DALI device does not support emergency tests.
Converter defectTrue, if the converter is defect.
Fault batteryTrue, if there is a battery fault.
Battery defectTrue, if the battery is defect.
Fault emergency lightTrue, if there is an emergency light failure.
Function test triggered but not executedTrue, if a function test was triggered but not finished.
Duration test triggered but not executedTrue, if a Duration test was triggered but not finished.
Function test failedTrue, if the function test failed.
Duration test failedTrue, if the duration test failed.
Test resultTest result: The raw data as received from the gateway. Time results have to be multiplied by 2 minutes; Battery charge status rannges from 0 to 255 and has to be converted to percentage.

...