Manufacturer | Type | Emergency | Fault General | Fault DALI | Fault Lamps | Fault Ballast | Fault Converter | Error Status Lamp/Ballast | Emergency Start | Emergency Result |
---|---|---|---|---|---|---|---|---|---|---|
Ipas | DaliControl e64 (plugin version) | yes | #8 | #9 | #12 | #14 | #16 | #20 | #176, offset: 11 | #177, offset: 11 |
DaliControl e64 | yes | #13 | #14 | #17 | #19 | #21 | #29 | #490, offset: 13 | #491, offset: 13 | |
DaliControl gc16 | no | #10 | #11 | #14 | #16 | NA | #20 | NA | NA | |
DaliControl gc16-2 | no | #12, #652 | #13, #653 | #16, #656 | #18, #658 | NA | #22, #662 | NA | NA | |
Merten | DALI gateway REG-K/1/16(64)/64/IP1 (plugin version) | yes | #8 | #9 | #12 | #14 | #16 | #20 | #176, offset: 11 | #177, offset: 11 |
DALI gateway REG-K/1/16(64)/64/IP1 | yes | #13 | #14 | #17 | #19 | #21 | #29 | #490, offset: 13 | #491, offset: 13 | |
DALI-Gateway Basic REG-K/1/16/64 | no | #10 | #11 | #14 | #16 | NA | #20 | NA | NA | |
DALI Gateway Basic REG-K/2/16/64 | no | #12, #652 | #13, #653 | #16, #656 | #18, #658 | NA | #22, #662 | NA | NA | |
Schneider | DALI gateway REG-K/1/16(64)/64/IP1 (plugin version) | yes | #8 | #9 | #12 | #14 | #16 | #20 | #176, offset: 11 | #177, offset: 11 |
DALI gateway REG-K/1/16(64)/64/IP1 | yes | #13 | #14 | #17 | #19 | #21 | #29 | #490, offset: 13 | #491, offset: 13 | |
DALI-Gateway Basic REG-K/1/16/64 | no | #10 | #11 | #14 | #16 | NA | #20 | NA | NA | |
DALI Gateway Basic REG-K/2/16/64 | no | #12, #652 | #13, #653 | #16, #656 | #18, #658 | NA | #22, #662 | NA | NA | |
DALI Gateway Basic REG-K/2/16/64 App Version 1.1 | n0 | #12, #1170 | #13, #1171 | #16, #1174 | #18, #1176 | NA | #22, #1180 | NA | NA | |
MDT | Dali Control IP 64 (plugin version) | yes | #8 | #9 | #12 | #14 | #16 | #20 | #176, offset: 11 | #177, offset: 11 |
Dali Control IP 64 | yes | #13 | #14 | #17 | #19 | #21 | #29 | #490, offset: 13 | #491, offset: 13 | |
Dali Control 32 | no | #12, #652 | #13, #653 | #16, #656 | #18, #658 | NA | #22, #662 | NA | NA | |
Dali Control 16 | no | #10 | #11 | #14 | #16 | NA | #20 | NA | NA | |
DALI Control 64 Gateway | no | #12 | #13 | #16 | #18 | NA | #22 | NA | NA | |
DALI Control 2x64 Gateway | no | #12, #1170 | #13, #1171 | #16, #1174 | #18, #1176 | NA | #22, #1180 | NA | NA | |
B.E.G. | DALI/KNX Gateway IP-N | yes | #8 | #9 | #12 | #14 | #16 | #20 | #176, offset: 11 | #177, offset: 11 |
Theben | DALI-Gateway KNX plus (plugin version) | yes | #8 | #9 | #12 | #14 | #16 | #20 | #176, offset: 11 | #177, offset: 11 |
DALI-Gateway KNX plus | yes | #13 | #14 | #17 | #19 | #21 | #29 | #490, offset: 13 | #491, offset: 13 | |
DALI-Gateway S64 KNX | no | #10 | #11 | #14 | #16 | NA | #20 | NA | NA | |
DALI-Gateway S128 KNX | no | #12, #652 | #13, #653 | #16, #656 | #18, #658 | NA | #22, #662 | NA | NA | |
DALI-Gateway S64 KNX App Version 2.1 | no | #12 | #13 | #16 | #18 | NA | #22 | NA | NA | |
DALI-Gateway S128 KNX App Version 2.1 | no | #12, #1170 | #13, #1171 | #16, #1174 | #18, #1176 | NA | #22, #1180 | NA | NA |
Info |
---|
Since the communication objects #12, #14 and #16 are only getting true when a configured threshold is exceeded, it is of utmost importance to configure them correctly. In general, it is recommended to use a threshold of 1 in order to see all lamp faults. |
...