Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

Within this configuration file, the VNET server that provides an interface to clients (e.g. NETx Visualization Editor) is configured.

Note

The parameters VNET.PIN and VNET.Password must always be present and set to an non empty value – otherwise the visualization editor is not able to connect to the Core Server.

Parameter

Description

Scope

Unit

Default value

VNET.NetworkCardIPAddress

Local IP address which is used for listening for secured VNET connections. Use this IP address within the configuration of VNET clients. If no value is specified, all interfaces will listen.

IP Address

None

IP of default network interface

VNET.NetworkSSLPortNumber

The TCP port which is used for listening for secured VNET connections. Use this port number within the configuration of VNET clients.

TCP Port

None

14532

VNET.Password

VNET SSL password that is checked by the server.

String

None

Mandatory

VNET.PIN

VNET SSL PIN that is checked by the clients.

String

None

Mandatory

VNET.ClientTimeout

Timeout of the VNET connections (Visualization Editor, Core Studio, clustering clients). If the client does not respond within the given time interval it will be disconnected from the Core Server.

1000 – 1000000

milliseconds

300000


Article applies to the following products

  • NETx BMS Platform

  • NETx MP Server