Table of Contents |
---|
...
Vendor | Name | Order number | Application |
---|---|---|---|
Gira
| DALI-Gateway | 1060 00 | DALI Gateway C00C13 |
DALI-Gateway | 1060 00 | DALI Gateway C00C11 | |
DALI-Gateway Plus | 2180 00 | DALI Gateway C00D11 | |
DALI-Gateway Plus | 2180 00 | DALI Gateway C00D12 | |
DALI-Gateway Tunable White Plus | 2108 00 | DALI Gateway TW C02011 | |
DALI-Gateway Tunable White Plus | 2108 00 | DALI Gateway TW C02012 |
Configuration
In addition to the common configuration options the following configuration options are available for each channel:
...
Warning |
---|
In order to use the object "Error per DALI device" within our LaMPS module, it is important to active the following options within the parameters of the device: |
The objects Fault General (#1524) and Emergency Lighting Failure (#1542) can be configured as passive or active feedback objects. If at least one of them is set as passive, "Poll Device" should be set to true.
...
Warning |
---|
If you want to use emergency tests for single battery powered emergency lights, it is of utmost importance to enable the external activate within the ETS parameters of the gateway: |
Functional description
This KNX/DALI gateway type provides a single DALI channel with up to 64 DALI devices. In addition to normal DALI testing, emergency lighting and extended tests for emergency lighting are supported, too.
...
In addition, the following device-specific items are available under the sub tree "Emergency":
item name | description |
---|---|
Emergency Lights On/Off | True, if the gateway is in emergency mode. |
Emergency Lighting Failure | True, if there is an emergency failure of at least one emergency DALI light. |
...
item name | description |
---|---|
Name | Human-readable name of the DALI device. The default name is "Device<number>". This name can be changed within the Device Name Mapping Definitions. |
Fault | True, if either a lamp or a device fault occurred. |
Fault Lamp | True, if there is a lamp fault. |
Fault Ballast | True, if there is a ballast fault. |
Fault Converter | (Emergency lighting only) True, if there is a converter fault. |
Test succeeded | True, if a response is received during the test. |
...