Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

Parameter

OPC.GroupAddressType

Description

It defines the format that is used to map KNX group addresses to server item IDs. 2Level - uses the two-level KNX group address format 3Level - uses the three-level KNX group address format

Scope

2level, 3level

Unit

None

Default value

3level

Parameter

OPC.PrefixedItemID

Description

It defines whether the leading "0"-characters shall be added to server item IDs. ON - defines that leading "0"characters are added to the item IDs of KNX group addresses OFF - defines that the item IDs of KNX group addresses do not contain leading "0"-characters

Scope

ON, OFF

Unit

None

Default value

ON

 

!Attention: In contrast to defined parameter within the studio, this has a crucial influence on the structure of all server item IDs.
The following examples represent the same KNX datapoint:
OPC.GroupAddressType: 2Level -> ITEM ID = "NETx\XIO\KNX\192.168.1.1\00/0513"
OPC.GroupAddressType: 3Level -> ITEM ID = "NETx\XIO\KNX\192.168.1.1\00/2/001" <table class="wrapped"> <colgroup> <col/> <col/> </colgroup> <tbody> <tr> <th> <p>
<em>Parameter</em> </p> </th> <th> <p>OPC.PrefixedItemID</p> </th> </tr> <tr> <td> <p> <em>Description</em> </p> </td> <td> <p> It defines whether the leading "0"-characters shall be added to server item IDs.
ON - defines that leading "0"characters are added to the item IDs of KNX group addresses
OFF - defines that the item IDs of KNX group addresses do not contain leading "0"-characters</p
</td> </tr> <tr> <td> <p> <em>Scope</em> </p> </td> <td> <p>ON, OFF</p> </td> </tr>
<tr> <td> <p> <em>Unit</em> </p> </td> <td> <p> None </p> </td> </tr> <tr> <td> <p>
<em>Default value</em> </p> </td> <td> <p> ON </p> </td> </tr> </tbody> </table> <p></p>

 

!Attention: This parameter has crucial influence on the structure of all server item IDs.
The following examples represent the same KNX datapoint:
OPC.PrefixedItemID: ON -> ITEM ID = "NETx\XIO\KNX\192.168.1.1\00/2/001"
OPC.PrefixedItemID: OFF -> ITEM ID = "NETx\XIO\KNX\192.168.1.1\0/2/1" <table class="wrapped"> <colgroup> <col/> <col/> </colgroup> <tbody> <tr> <th> <p>
<em>Parameter</em> </p> </th> <th> <p>OPC.AsyncTimeout</p> </th> </tr> <tr> <td>
<p> <em>Description</em> </p> </td> <td> <p>

 

Parameter

OPC.AsyncTimeout

Description

It defines the timeout value for asynchronous OPC queries. If no answer to an OPC query is received within this time interval, the quality of all queried datapoints will be set to UNCERTAIN.

...

Scope

1 - 60

Unit

seconds

Default value

5

Parameter

OPC.AsyncReadFromDevice

Description

It specifies whether the response data of the asynchronous OPC value read queries ("READ") shall be read from the server's data base, or whether it shall directly be retrieved from the field device.

...

ON - the field devices are queried

...

OFF - the values are read from the server's data base

...

Scope

ON, OFF

Unit

None

Default value

OFF

Parameter

OPC.AsyncRefreshFromDevice

Description

It specifies whether the response data of the asynchronous OPC value refresh queries ("REFRESH") shall be read from the server's data base, or whether it shall directly be retrieved from the field device.

...

ON - the field devices are queried

...

OFF - the values are read from the server's data base

...

Scope

ON, OFF

Unit

None

Default value

OFF

Parameter

OPC.ShowETSStructure

Description

It specifies whether to show an ETS like structure within the server item tree

...

ON - shows the ETS like structure

...

OFF - shows the NXA like

...

structure

Scope

ON, OFF

Unit

None

Default value

OFF

Parameter

OPC.QualityForValueNotSet

Description

It specifies which OPC Quality value shall be used for item values that are not yet set.

...

Scope

UNCERTAIN, BAD, NOT_

...

CONNECTED

Unit

None

Default value

UNCERTAIN

Parameter

OPC.Delimiter

Description

It specifies which delimiter shall be used for the item IDs within the server item tree.

...

Scope

String (" not allowed)

...

Unit

None

Default value

\

 

! Following OPC parameters are available only for compatibility reasons. In future versions they may vanish. <table class="wrapped"> <colgroup> <col/> <col/> </colgroup> <tbody> <tr> <th> <p>
<em>Parameter</em> </p> </th> <th> <p>OPC.AsyncWriteConfirmation</p> </th> </tr>
<tr> <td> <p> <em>Description</em> </p> </td> <td> <p>

Parameter

OPC.AsyncWriteConfirmation

Description

It specifies whether the response data of the asynchronous OPC value write queries ("WRITE") shall be read from the server's data base, or whether it shall directly be retrieved from the field device.

...

ON - the field devices are queried

...

OFF - the values are read from the server's data

...

base

Scope

ON, OFF

Unit

None

Default value

OFF

 

!Attention: If the parameter is set on "ON", each OPC "WRITE" command will result in sending up telegrams to the field network. In the case of KNX, up to three KNX telegrams are sent.

<table class="wrapped"> <colgroup> <col/> <col/> </colgroup> <tbody> <tr> <th> <p>
<em>Parameter</em> </p> </th> <th> <p>OPC.RefreshOnEqualValue</p> </th> </tr> <tr> <td> <p> <em>Description</em> </p> </td> <td> <p>  

Parameter

OPC.RefreshOnEqualValue

Description

It specifies whether OPC "OnDataChange" events are generated by incoming values from the field level even if the values are unchanged.

...

ON - the "OnDataChange" of events will be generated

...

OFF - the "OnDataChange" of events will be generated only with changes of

...

value

Scope

ON, OFF

Unit

None

Default value

ON

 

Example:
If the server receives two KNX telegrams with same value and same address (IP + KNX group address) and the option "OPC.RefreshOnEqualValue" is set to "OFF", the OPC "OnDataChange" event is generated only for the first telegram, since the second telegram does not cause a change of value of the datapoint. If this option is set on "ON", then two OPC "OnDataChange" events are generated.
 

!Attention: Use the following option only with caution! <table

class="wrapped"> <colgroup> <col/> <col/> </colgroup> <tbody> <tr> <th> <p>
<em>Parameter</em> </p> </th> <th> <p>OPC.AllValuesValid</p> </th> </tr> <tr> <td> <p> <em>Description</em> </p> </td> <td> <p>  

Parameter

OPC.AllValuesValid

Description

If set to "'ON"', server items always have the quality "'GOOD"', even if their quality is "'BAD"' or "'UNCERTAIN"'. This option can be used for limited OPC clients that are not aware of OPC qualities other than "'GOOD"'.

...

Scope

ON, OFF

Unit

None

Default value

OFF