Parameter | SYS.Historizing |
---|---|
Description | Enables or disables the storing of historical values into the SQL database. |
Scope | ON, OFF |
Unit | None |
Default value | ON |
Parameter | SYS.BackupHistorizing |
---|---|
Description | If enabled, the backup server also stores historical values in the historical database even if the backup server is inactive. |
Scope | ON, OFF |
Unit | None |
Default value | OFF |
Parameter | SYS.UseTelegramDataFile |
---|---|
Description | It specifies whether a virtual image of the plant (i.e. the values of all defined datapoints) is written to disk. |
Scope | ON, OFF |
Unit | None |
Default value | ON |
Parameter | SYS.SendVirtualTelegrams |
---|---|
Description | Enables or disables the sending of telegrams for KNX main group addresses above 15. |
Scope | ON, OFF |
Unit | None |
Default value | OFF |
Parameter | SYS.MaxSizeOfTelegramLogFile |
---|---|
Description | It specifies the maximum size of the telegram log file. |
Scope | 1 - 1000 |
Unit | Megabyte |
Default value | 10 |
Parameter | SYS.EnableDeviceManager |
---|---|
Description | This parameter enables the physical KNX device management. ON - the physical device management is enabled OFF - the physical device management is disabled |
Scope | ON, OFF |
Unit | None |
Default value | ON |
Parameter | SYS.GenerateRandomValues |
---|---|
Description | If the server is running in simulation mode and this parameter is set to "ON", the server generates random values for all server items. ON - the server generates random values if the server is running OFF - The server does not generate random values |
Scope | ON, OFF |
Unit | None |
Default value | ON |
Parameter | SYS.EnableOperationTime |
---|---|
Description | The server will calculate the operation time in seconds of KNX datapoints that are of type EIS1. ON - the operation time calculation is enabled OFF - the operation time calculation is disabled |
Scope | ON, OFF |
Unit | None |
Default value | OFF |
Parameter | SYS.GeoLatitude |
---|---|
Description | This parameter specifies the geographic latitude in degrees (+ is used for north, - for south) |
Scope | 0 - 360 |
Unit | degrees |
Default value | 0 |
Parameter | SYS.GeoLongitude |
---|---|
Description | This parameter specifies the geographic longitude in degrees (+ is used for east, - for west) |
Scope | 0 - 360 |
Unit | degrees |
Default value | 0 |
Parameter | SYS.GeoElevation |
---|---|
Description | It specifies the geographic elevation in meters. |
Scope | 0 - 10000 |
Unit | meters |
Default value | 0 |
! Following SYSTEM parameters are available only for compatibility reasons. In future versions they may vanish.
Parameter | SYS.GatewayConnectionTimeout |
---|---|
Description | It specifies the timeout value for availability check of the connected KNXnet/IP routers. |
Scope | 10 - 10000 |
Unit | milliseconds |
Default value | 500 |
Parameter | SYS.GatewayConnectionTimeoutAttemptCount |
---|---|
Description | It specifies the number of call attempts for the availability check of the connection of the connected KNXnet/IP routers in the case of an interruption. |
Scope | 1 - 10 |
Unit | None |
Default value | 3 |
Parameter | SYS.CodePage |
---|---|
Description | Defines the code page that is used within the NETx BMS Core Server. |
Scope | |
Unit | None |
Default value | 1250 |
Parameter | SYS.SpinLogFile |
---|---|
Description | ON - the system log file switches to a new file every day. OFF - the system log file remains in the same file as long as the server is running. |
Scope | ON, OFF |
Unit | None |
Default value | OFF |