Parameter

KNX.ShowUndefinedTelegrams

Description

If this parameter is set, received KNX telegrams that have an unknown KNX group address (i.e. a group address that is not defined within the server) will be shown in the message window of the NETx BMS Core Studio. ON - shows undefined KNX telegrams OFF - not activated

Scope

ON, OFF

Unit

None

Default value

OFF

 


Info

! Following KNX parameters are available only for compatibility reasons. In future versions they may vanish.

(question)TODO : Paramentes exist ?

Parameter

KNX.RefreshAllValuesOnConnect

Description

If a KNXnet/IP router is reconnecting to the server, the server can poll the current value of all datapoints that are assigned to this router. ON - the KNX datapoints are polled after a reconnect OFF - not activated

Scope

ON, OFF

Unit

None

Default value

OFF

...

Parameter

KNX.CyclicRefreshAllValues

Description

It is possible that the system automatically updates the internal data base in defined time intervals. The updates are done by sending cyclic KNX "READ" telegrams ON - automatic updating is activated OFF - not activated

Scope

ON, OFF

Unit

None

Default value

OFF

 


Info

!Attention: Note that activating cyclic refreshing of KNX datapoints may cause high amount of network traffic that may stress the connected KNX lines.

 

Parameter

KNX.CyclicRefreshAllValuesInterval

Description

It specifies the time interval that is used for the cyclic refresh mechanism. Note that all defined KNX datapoints are queried during a refresh. Therefore, this interval has to be chosen depending on the amount of KNX datapoints within the project. If the value is too small, the previous refresh process may not be finish and thus it will overlap with the next.

Scope

5 - 86400

Unit

seconds

Default value

10

...