Parameter

SYS.

Historizing

Description

Enables or disables the storing of historical values into the SQL database.

Scope

ON, OFF

Unit

None

Default value

ON

Parameter

SYS.BackupHistorizing

Description

If enabled, the backup server also stores historical values in the historical database even if the backup server is inactive.

Scope

ON, OFF

Unit

None

Default value

OFF

Parameter

SYS.

UseTelegramDataFile

Description

It specifies whether a virtual image of the plant (i.e. the values of all defined datapoints) is written to disk.

Scope

ON, OFF

Unit

None

Default value

ON


Parameter

SYS.SendVirtualTelegrams

Description

Enables or disables the sending of telegrams for KNX main group addresses above 15.

Scope

ON, OFF

Unit

None

Default value

OFF

...

Parameter

SYS.MaxSizeOfTelegramLogFile

Description

It specifies the maximum size of the telegram log file.

Scope

1 - 1000

Unit

Megabyte

Default value

10

...


Parameter

SYS.SpinTelegramFile

Description

If enabled a new telegram log file is created every day.

Scope

ON, OFF

Unit

None

Default value

ON

...

Parameter

SYS.EnableDeviceManager

Description

This parameter enables the physical KNX device management. ON - the physical device management is enabled OFF - the physical device management is disabled

Scope

ON, OFF

Unit

None

Default value

ON


Parameter

SYS.OPCInterfaceEnabled

Description

Enables the OPC Server. For security reasons, default is OFF.

Scope

ON, OFF

Unit

None

Default value

OFF


Parameter

SYS.GenerateRandomValues

Description

If the server is running in simulation mode and this parameter is set to "ON", the server generates random values for all server items. ON - the server generates random values if the server is running OFF - The server does not generate random values

Scope

ON, OFF

Unit

None

Default value

ON

...