Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.


Parameter
NameDescriptionScopeUnitDefaultNotes
SYS.SendVirtualTelegrams

Description

Enables or disables the sending of telegrams for KNX main group addresses above 15.

Scope

ON, OFF
Unit
None

Default value

OFF

Parameter


SYS.MaxSizeOfTelegramLogFile

Description

It specifies
Specifies the maximum size of the telegram log file.
ScopeDefault value
1 - 1000

Unit

Megabyte

MB10

Parameter


SYS.SpinTelegramFile

Description

If enabled a new telegram log file is created every day.

Scope

ON, OFF
Unit
None

Default value

ON

Parameter


SYS.EnableDeviceManager

Description

This parameter enables

Enables the physical KNX device management. ON - the physical device management is enabled OFF - the physical device management is disabled

Scope

ON, OFF

Unit

None
Default value
ON
Parameter

SYS.OPCInterfaceEnabled

Description

Enables the OPC Server.
For security reasons, default is OFF.

Scope

ON, OFF
Unit
None

Default value

ON
Parameter

SYS.GenerateRandomValues

Description

If the server is running in simulation mode and this parameter is set to "ON", the server generates random values for all server items. ON - the server generates random values if the server is running OFF - The server does not generate random values

Scope

ON, OFF

Unit

None
Default value
ON
Parameter

SYS.EnableOperationTime
Description
The server will calculate the operation time in seconds of KNX datapoints that are of type EIS1. ON - the operation time calculation is enabled OFF - the operation time calculation is disabled

Scope

ON, OFF

Unit

None

Default value

OFF
Parameter

SYS.CodePage

Description

Defines the code page that is used within the NETx BMS Core Server.
Scope
1 - 65535

Unit

None
Default value
1250
Parameter

SYS.LoggingLevel

Description

System logging level for providing additional output to server logs

Scope

-65535 - 65535

Unit

None

Default value

0

Parameter


SYS.GeoLatitude

Description

This parameter specifies
Specifies the geographic latitude in degrees (+ is used for north, - for south)

Scope

0 - 360
Unit
degrees

Default value

0

Parameter


SYS.GeoLongitude

Description

This parameter specifies
Specifies the geographic longitude in degrees (+ is used for east, - for west)
Scope
0 - 360

Unit

degrees

Default value

0
Parameter

SYS.GeoElevation

Description

It specifies
Specifies the geographic elevation in meters.

Scope

Default value

0 - 10000

Unit

meters

m0


Info
! Following SYSTEM parameters are available only for compatibility reasons. In future versions they may vanish.

Parameter


SYS.GatewayConnectionTimeout

Description

It specifies
Specifies the timeout value for availability check of the connected KNXnet/IP routers.

Scope

Parameter
10 - 10000

Unit

milliseconds

Default value

500

ms500
SYS.GatewayConnectionTimeoutAttemptCount

Description

It specifies
Specifies the number of call attempts for the availability check of the connection of the connected KNXnet/IP routers in the case of an interruption.
Scope
1 - 10
Unit
None
Default value
3
Parameter

SYS.SpinLogFile

Description

ON - the system log file switches to a new file every day. OFF - the system log file remains in the same file as long as the server is running.

Scope

ON, OFF
Unit
None
Default value
OFF


Article applies to the following products:

...