Name | Description | Scope | Unit | Default | Notes |
---|---|---|---|---|---|
SYS.SendVirtualTelegrams |
Description
Enables or disables the sending of telegrams for KNX main group addresses above 15. |
Scope
ON, OFF |
None |
Default value
OFF |
Parameter
SYS.MaxSizeOfTelegramLogFile |
Description
Specifies the maximum size of the telegram log file. |
1 - 1000 |
Unit
Megabyte
MB | 10 |
Parameter
SYS.SpinTelegramFile |
Description
If enabled a new telegram log file is created every day. |
Scope
ON, OFF |
None |
Default value
ON |
Parameter
SYS.EnableDeviceManager |
Description
Enables the physical KNX device management. ON - the physical device management is enabled OFF - the physical device management is disabled |
ON, OFF |
Unit
None |
ON |
SYS.OPCInterfaceEnabled |
Description
Enables the OPC Server. |
Scope
ON, OFF |
None |
Default value
ON |
SYS.GenerateRandomValues |
Description
If the server is running in simulation mode and this parameter is set to "ON", the server generates random values for all server items. ON - the server generates random values if the server is running OFF - The server does not generate random values |
Scope
ON, OFF |
Unit
None |
ON |
SYS.EnableOperationTime |
The server will calculate the operation time in seconds of KNX datapoints that are of type EIS1. ON - the operation time calculation is enabled OFF - the operation time calculation is disabled |
Scope
ON, OFF |
Unit
None |
Default value
OFF |
SYS.CodePage |
Description
Defines the code page that is used within the NETx BMS Core Server. |
1 - 65535 |
Unit
None |
1250 |
SYS.LoggingLevel |
Description
System logging level for providing additional output to server logs |
Scope
-65535 - 65535 |
Unit
None |
Default value
0 |
Parameter
SYS.GeoLatitude |
Description
Specifies the geographic latitude in degrees (+ is used for north, - for south) |
Scope
0 - 360 |
degrees |
Default value
0 |
Parameter
SYS.GeoLongitude |
Description
Specifies the geographic longitude in degrees (+ is used for east, - for west) |
0 - 360 |
Unit
degrees |
Default value
0 |
SYS.GeoElevation |
Description
Specifies the geographic elevation in meters. |
Scope
Default value
0 - 10000 |
Unit
meters
m | 0 | ||||||
|
Parameter
SYS.GatewayConnectionTimeout |
Description
Specifies the timeout value for availability check of the connected KNXnet/IP routers. |
Scope
10 - 10000 |
Unit
milliseconds
Default value
500
ms | 500 | |
SYS.GatewayConnectionTimeoutAttemptCount |
Description
Specifies the number of call attempts for the availability check of the connection of the connected KNXnet/IP routers in the case of an interruption. |
1 - 10 |
None |
3 |
SYS.SpinLogFile |
Description
ON - the system log file switches to a new file every day. OFF - the system log file remains in the same file as long as the server is running. |
Scope
ON, OFF |
None |
OFF |