Location: <WorkspaceDirectory>\DataFiles\nxaGatewayDefinitions.40.dat
...
The structure of the gateway definition file is as follows:'Syntax of the Gateway Definition Table:
'IP Address;Type;Port;Name;Locality;Description ;Options'192.168.1.2;NETIP;3671;Router1;;;;;;;
Each line – except comment lines that start with ' – defines a single KNXnet/IP gateway.
Info |
---|
! The virtual "BROADCAST" gateway is added by the system and must not be defined in the table. |
...
IP | This attribute specifies Specifies the IP address of the KNXnet/IP gateway. |
The IP address is also used to uniquely identify the gateway within the server. Therefore, it must be unique within the whole network. | IP address | None |
|
2 | Gateway Type |
Enum This attributes represents the | The type of the KNXnet/IP gateway. Supported types are - SEC_NETIP: secure KNXnet/IP tunnelling
- NETIP: native KNXnet/IP tunnelling
- NETIP_ROUTING: native KNXnet/IP routing
| SEC_NETIP, NETIP, NETIP_ROUTING | None |
|
3 | Port |
UDP or TCP port | The UDP or TCP port number which is used to connect to the gateway. | UDP or TCP port number | None |
|
4 | Name |
String | It is used to give the gateway a A unique human-readable name |
(can be any user-defined string). | String | None | The gateway's IP address. |
5 | Locality |
String | This attribute can be used to specify the location of the gateway (can be any user-defined string). | String | None |
|
6 | Description |
StringThe phys. | This attribute can be used to specify a human-readable text that further describes the gateway (can be any user-defined string). | String | None |
|
7 | Source phys. KNX Address |
KNX phys. address | The physical KNX address used by the |
NETx BMS Core Server when sending telegrams. Only used for KNXnet/IP routing. | KNX phys. address | None |
|
8 | Network Card IP Address |
IP | The local network card IP address used by the |
NETx BMS Core Server. Only used for KNXnet/IP routing. | IP | None |
|
9 | Management Code |
String | The management code used for authentication to a secure KNXnet/IP tunnelling device. This must be identical to the code used within the ETS. | String | None |
|
10 | Authentication Code |