Column | Description |
---|---|
Timeout | Value in ms, used as parameter when reading a GridVis value. |
Timeliness | Value in ms, used as parameter when reading a GridVis value. |
Ignore item quality | When set to active (checked), unsuccessful HTTP requests will NOT set the data point to "UNCERTAIN" within the NETx Server. The last valid value will remain. |
Ignore NaN values | When set to active (checked), received "NaN" values will be ignored. This means that a "NaN" value will not set the data item to "UNCERTAIN" in NETx Server. The last valid value will remain. |
HTTP Timeout (ms) | Value in ms, used for HTTP requests. |
Recommended settings:
Info |
---|
Changes in the driver configuration will be immediately effective without restarting the server. |
...
- OPC DA: all Server Items are available as OPC Items via OPC DA.
- OPC UA: in addition to "classical" OPC DA, the NETx Server has an OPC UA interface. This interface has to be installed with the Extension Manager within the studio > Extensions > Manager > Start Extension Manager.
- oBIX: Is an open, standardized web interface for home and building automation. This interface has to be installed with the Extension Manager within the studio > Extensions > Manager > Start Extension Manager.
- BACnet: Server Items can be read as BACnet objects from BACnet clients via BACnet/IP.
Article applies to the following products:
- NETx BMS Platform
- NETx Multi Protocol Server
- NETx BMS Server 2.0