ColumnDescription
TimeoutValue in ms, used as parameter when reading a GridVis value. 
TimelinessValue in ms, used as parameter when reading a GridVis value.
Ignore item qualityWhen set to active (checked), unsuccessful HTTP requests will NOT set the data point to "UNCERTAIN" within the NETx Server. The last valid value will remain.  
Ignore NaN valuesWhen set to active (checked), received "NaN" values will be ignored. This means that a "NaN" value will not set the data item to "UNCERTAIN" in NETx Server. The last valid value will remain.  
HTTP Timeout (ms)Value in ms, used for HTTP requests. 

Recommended settings:

Image Added

Info

Changes in the  driver configuration will be immediately effective without restarting the server. 

...

  • OPC DA: all Server Items are available as OPC Items via OPC DA.
  • OPC UA: in addition to "classical" OPC DA, the NETx Server has an OPC UA interface. This interface has to be installed with the Extension Manager within the studio > Extensions > Manager > Start Extension Manager.
  • oBIX: Is an open, standardized web interface for home and building automation. This interface has to be installed with the Extension Manager within the studio > Extensions > Manager > Start Extension Manager.
  • BACnet: Server Items can be read as BACnet objects from BACnet clients via BACnet/IP.

Article applies to the following products:

  • NETx BMS Platform
  • NETx Multi Protocol Server
  • NETx BMS Server 2.0