Table of Contents |
---|
...
OPC UA extension is available through Extension Manager. When the BMS Core Studio is stopped, the Extension Manager can be started from the BMS Studio menu Extensions / Manager / Start extension manager...
- Open the Extension Manager on the PC where you have the Internet connection.
- Navigate to the "Not installed" tab. Select the "OPC UA". Afterwards, press the "Install" button
After a successful installation the confirmation appears:
...
Integrate data points from another OPC UA Server
Adding Servers:
The NETx Server provides a OPC UA Client module to integrates data points from other OPC UA Servers. After installing the plugin, in the Modules>OPC UA>Server definitions. This menu is corresponding with adding another OPC UA Servers to the BMS Platform.
Parameter | Description |
---|---|
Name | The given name of the OPC UA Server in BMS Server. |
Path | The generated Path in Item Tree. |
URL | The URL of the OPC UA Server. |
User Security | To enable a secure connection. |
Add Unknown CertifcatesUnknown Certificates | To enable Unknown Certificates(by default enabled). |
Username | If the OPC UA Server requires Authentication with a Username and a Password. |
Password | If the OPC UA Server requires Authentication with a Username and a Password. |
Write timestamps | Choose which timestamp to write. |
...
Adding data points:
In Server definitions Server has been configured. Now OPC UA data point can be defined.This is done within the "Modules>OPC UA> Data point definitions" .