Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

Architecture

The NETx BMS Platfrom provides the possibility It is possible to integrate event information from Salto online door locks. The following figure shows how the integration has to be done.

Salto_Integration.pngImage RemovedImage Added

Salto door locks are using a wireless communication protocol which is based on ZigBee. In order to retrieve information like door events, ZigBee/IP gateways are required. These gateways are provided by Salto and have the aim to translate ZigBee packet into IP packets for the local area network (LAN). Depending on the project multiple ZigBee gateways are needed.

...

Then, the used doors have to be created. This is done within the "Door definitions" within the menu "Modules" -> "Salto".

FieldDescription
Door name*Must exactly contain the same name which are used within the Salto system
Door ExtID*Must exactly contain the same name which are used within the Salto system
PathDefine an optional structure within the item tree
Description Provide additional information which is stored within the item property



(plus)SC

After having defined all doors, the NETx BMS Core Server has to be restarted. Afterwards, the configured doors are shown within the item tree under the sub tree "NETx\XIO\SALTO".

...

The most important information is the "Operation ID" which indicates the event type. This ID can be linked to an XLogic command or LUA task in order to trigger some actions like changing a data point (e.g. trigger a lighting scene). The following table gives an overview of all "Operation IDs" and their meaning:


Operation ID

Description

Operation ID

Description

8

New renovation code for key (online).
16Door opened: inside handle.
17Door opened: key.
18Door opened: key and keyboard.
19Door opened: multiple guest key.
20Door opened: unique opening.
21Door opened: switch.
22Door opened: mechanical key.
25Door opened: PPD.
26Door opened: keyboard.
27Door opened: spare card (hotel).
28Door opened: online command.
29Door most probably opened: key and PIN.
33Door closed: key.
34Door closed: key and keyboard.
35Door closed: keyboard.
36Door closed: switch.
37Key inserted (energy saving device).
38Key removed (energy saving device).
39Room prepared (energy saving device).
40Start of privacy.
41End of privacy.
49Start of office mode.
50End of office mode.
51Hotel guest cancelled.
54Door programmed with spare key.
55New hotel guest key.
56Start of forced opening (online).
57End of forced opening (online).
58Start of forced closing (online).
59End of forced closing (online).
60Alarm: intrusion (online).
61Alarm: tamper (online)
62Door left opened (DLO).
63End of DLO (door left opened).
64End of intrusion.
65Start of office mode (online).
66End of office mode (online).
67End of tamper.
68Automatic change.
69Key updated in "out of site" mode (online).
70Expiration automatically extended (offline).
72Online peripheral updated.
76Key updated (online).
78Key deleted (online).

79

Door has lost communication with the Salto software.
80Door has re-established communication with the Salto software.
81Opening not allowed: key no activated.
82Opening not allowed: key expired.
83Opening not allowed: key out of date.
84Opening not allowed: key not allowed in this door.
85Opening not allowed: out of time.
87Opening not allowed: key does not override privacy.
88Opening not allowed: old hotel guest key.
89Opening not allowed: hotel guest key cancelled.
90Opening not allowed: antipassback.
92Opening not allowed: no associated authorization.
93Opening not allowed: invalid PIN.
95Opening not allowed: door in emergency state.
96Opening not allowed: key cancelled.
97Opening not allowed: unique opening key already used.
98Opening not allowed: key with old renovation number.
99Warning: key has not been completely updated (online).
100Opening not allowed: run out of battery.
101Opening not allowed: unable to audit on the key.
102Opening not allowed: locker occupancy timeout.
103Opening not allowed: denied by host.
104Blacklisted key deleted.
107Opening not allowed: key with data manipulated.
111Closing not allowed: door in emergency state.
112New renovation code.
113PPD connection.
114Time modified (daylight saving time).
115Low battery level.
116Incorrect clock value.
117RF Lock date and time updated.
118RF Lock updated.
1000The Salto software has re-established communication with the door.
1001The Salto software has lost communication with the door.
2000Guest new key
2001Guest copy key