Architecture
The NETx BMS Platfrom provides the possibility It is possible to integrate event information from Salto online door locks. The following figure shows how the integration has to be done.
Salto door locks are using a wireless communication protocol which is based on ZigBee. In order to retrieve information like door events, ZigBee/IP gateways are required. These gateways are provided by Salto and have the aim to translate ZigBee packet into IP packets for the local area network (LAN). Depending on the project multiple ZigBee gateways are needed.
...
Then, the used doors have to be created. This is done within the "Door definitions" within the menu "Modules" -> "Salto".
Field | Description |
---|---|
Door name* | Must exactly contain the same name which are used within the Salto system |
Door ExtID* | Must exactly contain the same name which are used within the Salto system |
Path | Define an optional structure within the item tree |
Description | Provide additional information which is stored within the item property |
SC
After having defined all doors, the NETx BMS Core Server has to be restarted. Afterwards, the configured doors are shown within the item tree under the sub tree "NETx\XIO\SALTO".
...
The most important information is the "Operation ID" which indicates the event type. This ID can be linked to an XLogic command or LUA task in order to trigger some actions like changing a data point (e.g. trigger a lighting scene). The following table gives an overview of all "Operation IDs" and their meaning:
Operation ID | Description |
---|---|
Operation ID | Description |
8 | New renovation code for key (online). |
16 | Door opened: inside handle. |
17 | Door opened: key. |
18 | Door opened: key and keyboard. |
19 | Door opened: multiple guest key. |
20 | Door opened: unique opening. |
21 | Door opened: switch. |
22 | Door opened: mechanical key. |
25 | Door opened: PPD. |
26 | Door opened: keyboard. |
27 | Door opened: spare card (hotel). |
28 | Door opened: online command. |
29 | Door most probably opened: key and PIN. |
33 | Door closed: key. |
34 | Door closed: key and keyboard. |
35 | Door closed: keyboard. |
36 | Door closed: switch. |
37 | Key inserted (energy saving device). |
38 | Key removed (energy saving device). |
39 | Room prepared (energy saving device). |
40 | Start of privacy. |
41 | End of privacy. |
49 | Start of office mode. |
50 | End of office mode. |
51 | Hotel guest cancelled. |
54 | Door programmed with spare key. |
55 | New hotel guest key. |
56 | Start of forced opening (online). |
57 | End of forced opening (online). |
58 | Start of forced closing (online). |
59 | End of forced closing (online). |
60 | Alarm: intrusion (online). |
61 | Alarm: tamper (online) |
62 | Door left opened (DLO). |
63 | End of DLO (door left opened). |
64 | End of intrusion. |
65 | Start of office mode (online). |
66 | End of office mode (online). |
67 | End of tamper. |
68 | Automatic change. |
69 | Key updated in "out of site" mode (online). |
70 | Expiration automatically extended (offline). |
72 | Online peripheral updated. |
76 | Key updated (online). |
78 | Key deleted (online). |
79 | Door has lost communication with the Salto software. |
80 | Door has re-established communication with the Salto software. |
81 | Opening not allowed: key no activated. |
82 | Opening not allowed: key expired. |
83 | Opening not allowed: key out of date. |
84 | Opening not allowed: key not allowed in this door. |
85 | Opening not allowed: out of time. |
87 | Opening not allowed: key does not override privacy. |
88 | Opening not allowed: old hotel guest key. |
89 | Opening not allowed: hotel guest key cancelled. |
90 | Opening not allowed: antipassback. |
92 | Opening not allowed: no associated authorization. |
93 | Opening not allowed: invalid PIN. |
95 | Opening not allowed: door in emergency state. |
96 | Opening not allowed: key cancelled. |
97 | Opening not allowed: unique opening key already used. |
98 | Opening not allowed: key with old renovation number. |
99 | Warning: key has not been completely updated (online). |
100 | Opening not allowed: run out of battery. |
101 | Opening not allowed: unable to audit on the key. |
102 | Opening not allowed: locker occupancy timeout. |
103 | Opening not allowed: denied by host. |
104 | Blacklisted key deleted. |
107 | Opening not allowed: key with data manipulated. |
111 | Closing not allowed: door in emergency state. |
112 | New renovation code. |
113 | PPD connection. |
114 | Time modified (daylight saving time). |
115 | Low battery level. |
116 | Incorrect clock value. |
117 | RF Lock date and time updated. |
118 | RF Lock updated. |
1000 | The Salto software has re-established communication with the door. |
1001 | The Salto software has lost communication with the door. |
2000 | Guest new key |
2001 | Guest copy key |