parametertypeoptional/mandatorycommunication objectdescriptiondefault
Fault GeneralItemIdMKNX Object #8, polledTrue, if there is an error for at least 1 DALI device.
Fault DALI ItemIdOKNX Object #9True, if there is a general short cut on the DALI bus
Fault LampsItemIdOKNX Object #12True, if the amount of faulty devices with a lamps fault exceeds the configured threshold.
Fault BallastItemIdOKNX Object #14True, if the amount of faulty devices with a ballast fault exceeds the configured threshold.
Fault ConverterItemIdOKNX Object #16, polledTrue, if the amount of faulty emergency lights with a converter fault exceeds the configured threshold.
Error Status Lamp/BallastItemIdMKNX Object #20

EmergencyTestTimeoutintO
Specifies how long the driver will wait between sending two emergency start requests.10 s


ManufacturerTypeEmergencyFault GeneralFault DALI Fault LampsFault BallastFault ConverterError Status Lamp/BallastEmergency StartEmergency Result
Ipas


DaliControl e64 (plugin version)yes#8#9#12#14#16#20

DaliControl e64yes#13#14#17#19#21#29

DaliControl gc16no#10#11#14#16NA#20

DaliControl gc16-2no
































































































Info
 Since the communication objects #12, #14 and #16 are only getting true when a configured threshold is exceeded, it is of utmost importance to configure them correctly. In general, it is recommended to use a threshold of 1 in order to see all lamp faults.

...