parameter | type | optional/mandatory | communication object | description | default |
---|
Fault General | ItemId | M | KNX Object #8, polled | True, if there is an error for at least 1 DALI device. |
|
Fault DALI | ItemId | O | KNX Object #9 | True, if there is a general short cut on the DALI bus |
|
Fault Lamps | ItemId | O | KNX Object #12 | True, if the amount of faulty devices with a lamps fault exceeds the configured threshold. |
|
Fault Ballast | ItemId | O | KNX Object #14 | True, if the amount of faulty devices with a ballast fault exceeds the configured threshold. |
|
Fault Converter | ItemId | O | KNX Object #16, polled | True, if the amount of faulty emergency lights with a converter fault exceeds the configured threshold. |
|
Error Status Lamp/Ballast | ItemId | M | KNX Object #20 |
|
|
EmergencyTestTimeout | int | O |
| Specifies how long the driver will wait between sending two emergency start requests. | 10 s |