parameter | type | optional/mandatory | communication objectPolled | description | default |
---|---|---|---|---|---|
Fault General | ItemId | M | KNX Object #8, polledyes | True, if there is an error for at least 1 DALI device. | |
Fault DALI | ItemId | O | KNX Object #9no | True, if there is a general short cut on the DALI bus | |
Fault Lamps | ItemId | O | KNX Object #12no | True, if the amount of faulty devices with a lamps fault exceeds the configured threshold. | |
Fault Ballast | ItemId | O | KNX Object #14no | True, if the amount of faulty devices with a ballast fault exceeds the configured threshold. | |
Fault Converter | ItemId | O | KNX Object #16, polledyes | True, if the amount of faulty emergency lights with a converter fault exceeds the configured threshold. | |
Error Status Lamp/Ballast | ItemId | M | KNX Object #20no | ||
EmergencyTestTimeout | int | O | Specifies how long the driver will wait between sending two emergency start requests. | 10 s |
...