ManufacturerTypeEmergencyFault GeneralFault DALI Fault LampsFault BallastFault ConverterError Status Lamp/BallastEmergency StartEmergency Result
Ipas


DaliControl e64 (plugin version)yes#8#9#12#14#16#20#176, offset: 11#177, offset: 11
DaliControl e64yes#13#14#17#19#21#29#490, offset: 13#491, offset: 13
DaliControl gc16no#10#11#14#16NA#20NANA
DaliControl gc16-2no#12, #652#13, #653#16, #656#18, #658NA#22, #662NANA
Merten

DALI gateway REG-K/1/16(64)/64/IP1 (plugin version)yes#8#9#12#14#16#20#176, offset: 11#177, offset: 11
DALI-Gateway Basic REG-K/1/16/64no#10#11#14#16NA#20NANA
DALI Gateway Basic REG-K/2/16/64no#12, #652#13, #653#16, #656#18, #658NA#22, #662NANA
Schneider

DALI gateway REG-K/1/16(64)/64/IP1 (plugin version)yes#8#9#12#14#16#20#176, offset: 11#177, offset: 11
DALI-Gateway Basic REG-K/1/16/64no#10#11#14#16NA#20NANA
DALI Gateway Basic REG-K/2/16/64no#12, #652#13, #653#16, #656#18, #658NA#22, #662NANA
MDTDali Control IP 64 (plugin version)yes#8#9#12#14#16#20

Dali Control IP 64yes#13#14#17#19#21#29#490, offset: 13#491, offset: 13
Dali Control 32








Dali Control 16








B.E.G.DALI/KNX Gateway IP-Nyes#8#9#12#14#16#20#176, offset: 11#177, offset: 11


Info
 Since the communication objects #12, #14 and #16 are only getting true when a configured threshold is exceeded, it is of utmost importance to configure them correctly. In general, it is recommended to use a threshold of 1 in order to see all lamp faults.

...