Since these gateways also support emergency lighting, it has to be distinguished between a normal DALI test and an emergency DALI test. For normal DALI testing, the following Server Items are available:
...
Include Page Normal DALI testing server items Normal DALI testing server items
For emergency DALI testing, the following Server Items are available under the sub tree "Emergency":
item name | description |
---|---|
Emergency Mode Active | True, if the gateway is in emergency mode. |
Emergency Lighting Failure | True, if there is an emergency failure of at least one emergency DALI light. |
Start Function Test | Used to trigger a function test for all emergency DALI lights. |
Start Duration Test | Used to trigger a duration test for all emergency DALI lights. |
Start Partial Duration Test | Used to trigger a partial duration test for all emergency DALI lights. |
Start Battery Test | Used to trigger a battery test for all emergency DALI lights. |
Stop Test | Used to stop a running test. |
Emergency Light Test Running | True, when an emergency DALI test is currently running. |
...