parameter | type | optional/mandatory | communication object | description | default |
---|---|---|---|---|---|
Fault General | ItemId | M | KNX Object #1524, polled | True, if there is an error for at least 1 DALI device. | |
Fault Short Circuit | ItemId | O | KNX Object #1527 | True, if there is a general short cut on the DALI bus. | |
Fault Power Failure | ItemId | O | KNX Object #1525 | True, if there is a power failure on the DALI bus. | |
Emergency Mode Active | ItemId | O | KNX Object #1541 | True, if DALI devices are in emergency mode. | |
Emergency Lighting Failure | ItemId | O | KNX Object #1542, polled | True, if there is an error for at least 1 emergency DALI device. This config element is optional. If it is not used, emergency lighting test features are not available. | |
Error per DALI Device | ItemId | M | KNX Object #1544 | KNX feedback object for DALI device errors. | |
EmergencyTestTimeoutEmergency Test Interval | int | O | Specifies how long the driver will wait between sending two emergency start requests. | 10 s |
...