Configuration

...

parametertypeoptional/mandatorycommunication objectdescriptiondefault
Fault LampsItemIdMKNX Object #17, polledTrue, if there is a lamp error for at least 1 DALI device.
Fault BallastItemIdMKNX Object #18, polledTrue, if there is a ballast error for at least 1 DALI device.
Fault DALIItemIdOKNX Object #19, polledTrue, if there is a general DALI error.
Diagnostics ItemIdMKNX Object #25Used to trigger a normal DALI request and to get the test result.
Emergency Test StartItemIdOKNX Object #31Used to trigger an emergency DALI test for a dedicated device.
Emergency Test ResultItemIdOKNX Object #33Used to get the result of an emergency DALI test.
Emergency Mode ActiveItemIdOKNX Object #35True, if the DALI emergency lighting mode is active.
Emergency Test IntervalintO
Specifies how long the driver will wait between sending two emergency start requests.10 s


Info

The ABB DGN/S 1.16.1 gateway uses emergency test start and result objects for all devices on one channel – there are no individual objects for each emergency ballast as it is for other gateways. Therefore, there will appear no entry within the Emergency Mapping Definitions. If the emergency configuration is enabled it will appear within the ABB DGN/S 1.16.1 gateway definition.

Functional Description

These KNX/DALI gateway types provide 1 with up to 64 DALI devices. In addition to normal DALI testing, they support emergency lighting and extended tests for emergency lighting too.

...

Info

Please keep in mind that these items will only appear when emergency testing is available for the gateway. For these KNX/DALI gateways the "Emergency Test Start (#32, #40 or #1154)" and "Emergency Test Result (#33, #42 or #1156)" objects must be available and configured in order to support emergency testing. Note that emergency testing is only available for self contained battery lamps.

...

For each configured DALI device, a sub tree with the name "Device<number>" is shown within the Server Item Tree. Each device has at least the following Server Items:

item namedescription
NameHuman-readable name of the DALI device. The default name is "Device<number>". This name can be changed within the Device Name Mapping Definitions. 
FaultTrue, if either a lamp or a device fault occurred.
Fault LampTrue, if there is a lamp fault.
Fault BallastTrue, if there is a ballast fault.
Fault Converter(Emergency lighting only) True, if there is a converter fault.
Test succeededTrue, if a response is received during the test.

...

If emergency functions are available, the following items are available in the sub tree "Emergency":

...