Configuration
...
parameter | type | optional/mandatory | communication object | description | default |
---|---|---|---|---|---|
Fault Lamps | ItemId | M | KNX Object #17, polled | True, if there is a lamp error for at least 1 DALI device. | |
Fault Ballast | ItemId | M | KNX Object #18, polled | True, if there is a ballast error for at least 1 DALI device. | |
Fault DALI | ItemId | O | KNX Object #19, polled | True, if there is a general DALI error. | |
Diagnostics | ItemId | M | KNX Object #25 | Used to trigger a normal DALI request and to get the test result. | |
Emergency Test Start | ItemId | O | KNX Object #31 | Used to trigger an emergency DALI test for a dedicated device. | |
Emergency Test Result | ItemId | O | KNX Object #33 | Used to get the result of an emergency DALI test. | |
Emergency Mode Active | ItemId | O | KNX Object #35 | True, if the DALI emergency lighting mode is active. | |
Emergency Test Interval | int | O | Specifies how long the driver will wait between sending two emergency start requests. | 10 s |
Info |
---|
The ABB DGN/S 1.16.1 gateway uses emergency test start and result objects for all devices on one channel – there are no individual objects for each emergency ballast as it is for other gateways. Therefore, there will appear no entry within the Emergency Mapping Definitions. If the emergency configuration is enabled it will appear within the ABB DGN/S 1.16.1 gateway definition. |
Functional Description
These KNX/DALI gateway types provide 1 with up to 64 DALI devices. In addition to normal DALI testing, they support emergency lighting and extended tests for emergency lighting too.
...
Info |
---|
Please keep in mind that these items will only appear when emergency testing is available for the gateway. For these KNX/DALI gateways the "Emergency Test Start (#32, #40 or #1154)" and "Emergency Test Result (#33, #42 or #1156)" objects must be available and configured in order to support emergency testing. Note that emergency testing is only available for self contained battery lamps. |
...
For each configured DALI device, a sub tree with the name "Device<number>" is shown within the Server Item Tree. Each device has at least the following Server Items:
item name | description |
---|---|
Name | Human-readable name of the DALI device. The default name is "Device<number>". This name can be changed within the Device Name Mapping Definitions. |
Fault | True, if either a lamp or a device fault occurred. |
Fault Lamp | True, if there is a lamp fault. |
Fault Ballast | True, if there is a ballast fault. |
Fault Converter | (Emergency lighting only) True, if there is a converter fault. |
Test succeeded | True, if a response is received during the test. |
...
If emergency functions are available, the following items are available in the sub tree "Emergency":
...