parametertypeoptional/mandatorycommunication objectdescriptiondefault
Fault LampsItemIdMKNX Object #17, polledTrue, if there is a lamp error for at least 1 DALI device.
Fault BallastItemIdMKNX Object #18, polledTrue, if there is a ballast error for at least 1 DALI device.
Fault DALIItemIdOKNX Object #19, polledTrue, if there is a general DALI error.
Diagnostics ItemIdMKNX Object #25#20Used to trigger a normal DALI request and to get the test result.
Emergency Test StartItemIdOKNX Object #31Used to trigger an emergency DALI test for a dedicated device.
Emergency Test ResultItemIdOKNX Object #33Used to get the result of an emergency DALI test.
Emergency Mode ActiveItemIdOKNX Object #35True, if the DALI emergency lighting mode is active.
Emergency Test IntervalintO
Specifies how long the driver will wait between sending two emergency start requests.10 s


Info

The ABB DGN/S 1.16.1 gateway uses emergency test start and result objects for all devices on one channel – there are no individual objects for each emergency ballast as it is for other gateways. Therefore, there will appear no entry within the Emergency Mapping Definitions. If the emergency configuration is enabled it will appear within the ABB DGN/S 1.16.1 gateway definition.

Functional Description

These KNX/DALI gateway types provide 1 with up to 64 DALI devices. In addition to normal DALI testing, they support emergency lighting and extended tests for emergency lighting too.

...