Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

Configuration

...

For emergency DALI testing, the following Server Items are available under the sub tree "Emergency":

item namedescription
Emergency Lights On/OffTrue, if the gateway is in emergency mode.
Emergency Lighting FailureTrue, if there is an emergency failure of at least one emergency DALI light.
Start Function TestUsed to trigger a function test for all emergency DALI lights.
Start Partial Duration TestUsed to trigger a partial duration test for all emergency DALI lights.
Start Duration TestUsed to trigger a duration test for all emergency DALI lights.
Start Battery TestUsed to trigger a battery test for all emergency DALI lights.
Stop TestUsed to stop a running test.
Emergency Lights Test RunningTrue, if an emergency DALI test is currently running.

...

item namedescription
NameHuman-readable name of the DALI device. The default name is "Device<number>". This name can be changed within the Device Name Mapping Definitions. 
FaultTrue, if either a lamp or a device fault occurred.
Fault LampTrue, if there is a lamp fault.
Fault BallastTrue, if there is a ballast fault.
Fault Converter(Emergency lighting only) True, if there is a converter fault.
Test succeededTrue, if a response is received during the test.

...