Configuration

...

The objects Fault General (#1524) and Error per DALI Device (#1544) needs to must be linked to a group address. Otherwise the DALI gateway will be seen considere as "not used" and therefore be ignored for the export.

...

For emergency DALI testing, the following Server Items are available under the sub tree "Emergency":

item namedescription
Emergency Lights On/OffTrue, if the gateway is in emergency mode.
Emergency Lighting FailureTrue, if there is an emergency failure of at least one emergency DALI light.
Start Function TestUsed to trigger a function test for all emergency DALI lights.
Start Partial Duration TestUsed to trigger a partial duration test for all emergency DALI lights.
Start Duration TestUsed to trigger a duration test for all emergency DALI lights.
Start Battery TestUsed to trigger a battery test for all emergency DALI lights.
Stop TestUsed to stop a running test.
Emergency Lights Test RunningTrue, if an emergency DALI test is currently running.

...

item namedescription
NameHuman-readable name of the DALI device. The default name is "Device<number>". This name can be changed within the Device Name Mapping Definitions. 
FaultTrue, if either a lamp or a device fault occurred.
Fault LampTrue, if there is a lamp fault.
Fault BallastTrue, if there is a ballast fault.
Fault Converter(Emergency lighting only) True, if there is a converter fault.
Test succeededTrue, if a response is received during the test.

...