Configuration

...

Include Page
Normal DALI testing server items
Normal DALI testing server items

Include Page
Emergency testing server items
For emergency DALI testing
Emergency testing server items

In addition, the following Server Items device-specific items are available under the sub tree "Emergency":

item namedescription
Emergency Lights On/OffTrue, if the gateway is in emergency mode.
Emergency Lighting FailureTrue, if there is an emergency failure of at least one emergency DALI light.
Start Function TestUsed to trigger a function test for all emergency DALI lights.
Start Partial Duration TestUsed to trigger a partial duration test for all emergency DALI lights.
Start Duration TestUsed to trigger a duration test for all emergency DALI lights.
Start Battery TestUsed to trigger a battery test for all emergency DALI lights.
Stop TestUsed to stop a running test.
Emergency Lights Test RunningTrue, if an emergency DALI test is currently running.


Info

Please keep in mind that these items will only appear when emergency testing is available for the gateway. For these KNX/DALI gateways at least one DALI device must support emergency lighting tests. This means that there must be a "Emergency Mapping Definition" for at least one DALI device. Note that emergency testing is only available for self contained battery lamps.

...

item namedescription
NameHuman-readable name of the DALI device. The default name is "Device<number>". This name can be changed within the Device Name Mapping Definitions. 
FaultTrue, if either a lamp or a device fault occurred.
Fault LampTrue, if there is a lamp fault.
Fault BallastTrue, if there is a ballast fault.
Fault Converter(Emergency lighting only) True, if there is a converter fault.
Test succeededTrue, if a response is received during the test.

...