For emergency DALI testing, the following Server Items are available under the sub tree "Emergency":

item name

description

Start Function TestUsed to trigger a function test for all emergency DALI lights.
Start Duration TestUsed to trigger a duration test for all emergency DALI lights.
Start Battery TestUsed to trigger a battery test for all emergency DALI lights.
Stop TestUsed to stop a running test.
Emergency Light
Test RunningTrue,
when
if an emergency DALI test is currently running.
FaultTrue, if an emergency test of at least 1 DALI light failed.
Last test faultedTrue, if "Last test faulted" of at least 1 DALI light is currently true.
Converter defectTrue, if "Converter defect" of at least 1 DALI light is currently true.
Battery fault or defectTrue, if "Battery fault or defect" of at least 1 DALI light is currently true.
Fault emergency lightTrue, if "Fault emergency light" of at least 1 DALI light is currently true.


Info

Please keep in mind that these items will only appear when emergency testing is available for the gateway. For these KNX/DALI gateways at least one DALI device must support emergency lighting tests. This means that there must be a "Emergency Mapping Definition" for at least one DALI device. Note that emergency testing is only available for self contained battery lamps.

...

item namedescription
Test RunningTrue, when an emergency DALI test is currently running.
Start Function TestUsed to trigger a function test for this device.
Start Duration TestUsed to trigger a duration test for this device.
Start Battery TestUsed to trigger a battery test for this device.
Stop TestUsed to stop a running test.
Last test was

Shows the type of the last test. 

value

description

0"No Test"
1"Function Test"
2"Partial duration test"
3"Duration test"
4"Battery test"
255"Test not supported"


Last test faultedTrue, if there was no test result response. This may be the case when the DALI does not support emergency tests.
Converter defectTrue, if the converter is defect.
Fault batteryTrue, if there is a battery fault.
Battery defectTrue, if the battery is defect.
Fault emergency lightTrue, if there is an emergency light failure.
Max time function test exceededTrue, if the maximum time for the function test exceeded.
Max time duration test exceededTrue, if the maximum time for the duration test exceeded.
Function test failedTrue, if the function test failed.
Duration test failedTrue, if the duration test failed.
Test resultTest result: The raw data as received from the gateway. Time results have to be multiplied by 2 minutes; Battery charge status is from 0 to 255 and has to be converted to percentage.

...