parametertypeoptional/mandatoryPolleddescriptiondefault
Fault GeneralItemIdMyesTrue, if there is an error for at least 1 DALI device.
Fault DALI ItemIdOnoTrue, if there is a general short cut on the DALI bus
Fault LampsItemIdOnoTrue, if the amount number of faulty devices with a lamps fault exceeds the configured threshold.
Fault BallastItemIdOnoTrue, if the amount number of faulty devices with a ballast fault exceeds the configured threshold.
Fault ConverterItemIdOyesTrue, if the amount the number of faulty emergency lights with a converter fault exceeds the configured threshold.
Error Status Lamp/BallastItemIdMno

Emergency Test IntervalintO
Specifies how long the driver will wait between sending two emergency start requests.10 s

...

item namedescription
KNX IP ConnectionThis Item reflects the KNXnet/IP tunneling connection to KNXnet/IP router or interface which is used to communicate with the KNX/DALI gateway.
FaultTrue, if there is either a DALI, lamp, or ballast fault.
Fault DALITrue, if there is a general short cut on the DALI bus.
Fault DevicesTrue, if there is a lamp or ballast fault for at least 1 DALI device.
Fault Lamp

True, if the amount number of lamp faults exceeds the configured threshold. If exceeded, LaMPS is starting to test all configured devices in order to see which device(s) have a fault. 

Fault BallastTrue, if the amount the number of ballast faults exceeds the configured threshold. If exceeded, LaMPS is starting to test all configured devices in order to see which device(s) have a fault. 
Fault ConverterTrue, if there is a converter fault of one or more DALI devices.  

...

For emergency DALI testing, the following Server Items are available under the sub tree "Emergency":

item name

description

Start Function TestUsed to trigger a function test for all emergency DALI lights.
Start Duration TestUsed to trigger a duration test for all emergency DALI lights.
Start Battery TestUsed to trigger a battery test for all emergency DALI lights.
Stop TestUsed to stop a running test.
Test RunningTrue, if an emergency DALI test is currently running.
FaultTrue, if an emergency test of at least 1 DALI light failed.
Last test faultedTrue, if "Last test faulted" of at least 1 DALI light is currently true.
Converter defectTrue, if "Converter defect" of at least 1 DALI light is currently true.
Battery fault or defectTrue, if "Battery fault or defect" of at least 1 DALI light is currently true.
Fault emergency lightTrue, if "Fault emergency light" of at least 1 DALI light is currently true.


Info

Please keep in mind that these items will only appear when emergency testing is available for the gateway. For these KNX/DALI gateways at least one DALI device must support emergency lighting tests. This means that there must be a "Emergency Mapping Definition" for at least one DALI device. Note that emergency testing is only available for self contained battery lamps.

...