parameter | type | optional/mandatory | Polled | description | default |
---|---|---|---|---|---|
Fault General | ItemId | M | yes | True, if there is an error for at least 1 DALI device. | |
Fault DALI | ItemId | O | no | True, if there is a general short cut on the DALI bus | |
Fault Lamps | ItemId | O | no | True, if the amount number of faulty devices with a lamps fault exceeds the configured threshold. | |
Fault Ballast | ItemId | O | no | True, if the amount number of faulty devices with a ballast fault exceeds the configured threshold. | |
Fault Converter | ItemId | O | yes | True, if the amount the number of faulty emergency lights with a converter fault exceeds the configured threshold. | |
Error Status Lamp/Ballast | ItemId | M | no | ||
Emergency Test Interval | int | O | Specifies how long the driver will wait between sending two emergency start requests. | 10 s |
...
item name | description |
---|---|
KNX IP Connection | This Item reflects the KNXnet/IP tunneling connection to KNXnet/IP router or interface which is used to communicate with the KNX/DALI gateway. |
Fault | True, if there is either a DALI, lamp, or ballast fault. |
Fault DALI | True, if there is a general short cut on the DALI bus. |
Fault Devices | True, if there is a lamp or ballast fault for at least 1 DALI device. |
Fault Lamp | True, if the amount number of lamp faults exceeds the configured threshold. If exceeded, LaMPS is starting to test all configured devices in order to see which device(s) have a fault. |
Fault Ballast | True, if the amount the number of ballast faults exceeds the configured threshold. If exceeded, LaMPS is starting to test all configured devices in order to see which device(s) have a fault. |
Fault Converter | True, if there is a converter fault of one or more DALI devices. |
...
For emergency DALI testing, the following Server Items are available under the sub tree "Emergency":
item name | description |
---|---|
Start Function Test | Used to trigger a function test for all emergency DALI lights. |
Start Duration Test | Used to trigger a duration test for all emergency DALI lights. |
Start Battery Test | Used to trigger a battery test for all emergency DALI lights. |
Stop Test | Used to stop a running test. |
Test Running | True, if an emergency DALI test is currently running. |
Fault | True, if an emergency test of at least 1 DALI light failed. |
Last test faulted | True, if "Last test faulted" of at least 1 DALI light is currently true. |
Converter defect | True, if "Converter defect" of at least 1 DALI light is currently true. |
Battery fault or defect | True, if "Battery fault or defect" of at least 1 DALI light is currently true. |
Fault emergency light | True, if "Fault emergency light" of at least 1 DALI light is currently true. |
Info |
---|
Please keep in mind that these items will only appear when emergency testing is available for the gateway. For these KNX/DALI gateways at least one DALI device must support emergency lighting tests. This means that there must be a "Emergency Mapping Definition" for at least one DALI device. Note that emergency testing is only available for self contained battery lamps. |
...