Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

Location:

<WorkspaceDirectory>\DataFiles\nxaKNXObjectDefinitions.dat


Info

! This definition file can also be generated using the ETS app import wizard (Studio → KNX → Inport NETx ETS App file ...) which generates the ETS object definitions from an exported ETS project.


Within this configuration file, the KNX communication objects as represented in the item tree are specified. The structure of the definition file is as follows:


'Syntax of the ETS Object Definition Table:
'Name;Object function;Device name;Path;Communication flag;Read flag;Write flag;Transmit flag;Update flag;Read on init flag;Physical address;IP address;Group addresses (first one is sending)
Output A;10: Switch;Room1 - Light HVAC Actuator;Demo_Case_Large\Buildings\BuildingA\Floor1\Cabinet1\3.1.1;T;F;T;F;F;F ;3.1.1;192.168.1.15;0/0/1@192.168.1.15
Output A;29: Status Switch;Room1 - Light HVAC Actuator;Demo_Case_Large\Buildings\BuildingA\Floor1\Cabinet1\3.1.1;T;T;F ;T;F;F;3.1.1;192.168.1.15;0/0/2@192.168.1.15
Output B;30: Switch;Room1 - Light HVAC Actuator;Demo_Case_Large\Buildings\BuildingA\Floor1\Cabinet1\3.1.1;T;F;T;F;F;F ;3.1.1;192.168.1.15;0/0/3@192.168.1.15
Output B;49: Status Switch;Room1 - Light HVAC Actuator;Demo_Case_Large\Buildings\BuildingA\Floor1\Cabinet1\3.1.1;T;T;F ;T;F;F;3.1.1;192.168.1.15;0/0/4@192.168.1.15
Each line – except comment lines that start with ' – defines a single communication object.
! The ETS object definitions within this file are automatically created by the NETx BMS App. Therefore, editing it manually is not necessary in general.
<tr> <td>1</td> <td>Name</td> <td></td> <td>






1Name
This parameter refers to the name of the communication object.

...

2Object function
Here the name of the function of the communication object is specified.

...

3Device name
This is the device name to which the communication object belongs to.

...

4Path
This column defines the path within the ETS view where the communication object is shown.

...

5Communication flag
The KNX communication flag of the communication object. For more information see ETS documentation.

...

6Read flag
The KNX read flag of the communication object. For more information see ETS documentation.

...

7Write flag
The KNX write flag of the communication object. For more information see ETS documentation.

...

8Transmit flag
The KNX transmit flag of the communication object. For more information see ETS documentation.

...

9Update flag
The KNX update flag of the communication object. For more information see ETS documentation.

...

10Read on init flag
The KNX read on init flag of the communication object. For more information see ETS documentation.

...

11Physical address
The physical address of the device where the communication object is located.

...

12Reserved
Not used.
13Group addresses (first one is sending)

...


The KNX group addresses that are linked to the communication object. The first group address is the sending group address i.e. the address which is used for send whenever the communication object changes its value.

...