Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.


...

Info
titleFile location

<WorkspaceDirectory>\DataFiles\xio.Modbus.DatapointDefinitions.dat

The Modbus interface provides the opportunity to read and write Modbus datapoints. The current version of the NETx BMS Core Server 24.0 support supports the handling of Modbus discrete inputs, coils, holding registers, and input registers. For more information see Section 4.9.3.

The encoding of Modbus datapoint types is vendor-specific. To be able to deal with the different vendor-specific encoding, configuration parameters to set the swapping of Words, Double Words, and Bits are available. These parameters can be defined for each device and for each datapoint. Furthermore, it is possible to specify the endianess that is used within the device (cf. Section 4.3.2.1).

Note that using the correct encoding settings is at utmost importance. If these parameters are incorrect, the corresponding values of the Modbus datapoints are interpreted, stored, and displayed in a wrong way. Furthermore, it has to be considered that these parameters are affecting each other. To choose the correct parameters please refer to the manual and datasheet of the used Modbus devices.

The structure of the Modbus datapoint definition file is as follows: ' Modbus datapoint configuration file
' DeviceName;ModbusType;Address;SubDataType;Size;Description;PollingInterval;Persistent;Historical;Synchronize; Wordswap;DWordswap;Bitswap
ModbusController1;discrete input;12416;bool;1;DI 1;10;F;F;F;F;T;F
ModbusController1;coil;12417;bool;1;DO 1;10;F;F;F;;;;;
ModbusController1;input register;12418;uint16;1;AI 1;10;F;F;F;F;;;;;
ModbusController1;holding register;12419;uint16;1;AO 1;10;F;F;F;F;;;;;
Each line – except comment lines that start with ' – defines a single Modbus datapoint.
<tr> <td>1</td> <td>DeviceName</td> <td></td> <td> This attribute refers to the name

 Col# Parameter DescriptionScopeUnitDefault
1Device nameName of the device which holds the datapoint. This name must match the device name used in the Modbus device

...

...




2Modbus DP typeData type of the data point.Modbus datapoint type

3AddressSpecifies the memory address of the Modbus

...

register.


4Data typeSpecifies the data type of Server Item that shall represent

...

the Modbus

...

data point.


5SizeSpecifies the size of the Modbus

...

data (only considered if DataType is set to "string" or "wstring"

...

).
byte
6DescriptionCan be used to specify a human-readable text that further describes the

...

data point. Optional.


7Polling intervalSpecifies the interval that is used to poll the value of the

...

data point.


8PersistentSpecifies whether the value of the datapoint is persistent (restored from the database after server start up ) or not.

...

boolean
F
10Synchronize

Specifies the synchronization behavior in a Main/Backup setup.

  • T: the value is synchronized between the main and backup server

...

  • .
  • F: the value is not synchronized between the main and backup server.
boolean
T
11WordswapCan be used to overwrite the Word Swap parameter of the Modbus device. If this parameter is set to "T" ("TRUE") or "F" ("FALSE"), the word swapping for this datapoint is overwritten. If this parameter is empty (or set to a value unequal to "T" or "F"), the word swapping specified in the device definition is used.

...



device setting
12DWordswapCan be used to overwrite the Double Word Swap parameter of the Modbus device. If this parameter is set to "T" ("TRUE") or "F" ("FALSE"), the double word swapping for this datapoint is overwritten. If this parameter is empty (or set to a value unequal to "T" or "F"), the double word swapping specified in the device definition is used.

...



device setting
13BitswapCan be used to overwrite the Bit Swap parameter of the Modbus device. If this parameter is set to "T" ("TRUE") or "F" ("FALSE"), the bit swapping for this datapoint is overwritten. If this parameter is empty (or set to a value unequal to "T" or "F"), the bit swap specified in the device definition is used.

...



device setting
14Read on ReconnectIf set to "T", a read request is sent

...

if the connection status of the gateway changes to ONLINE.boolean
F
15Write ModeIf not specified, the write mode that is defined within the Modbus Device Definition is used.

...



device setting