Configuration
...
item name | description |
---|---|
KNX IP Connection | This Item reflects the KNXnet/IP tunneling connection to KNXnet/IP router or interface which is used to communicate with the KNX/DALI gateway. |
Fault | True, if there is either a power failure, short circuit, lamp, ballast or converter fault. |
Fault Devices | True, if there is a lamp, ballast or converter failure for at least 1 DALI device. |
Fault Lamp | True, if there is a lamp fault of one or more DALI devices. |
Fault Ballast | True, if there is a ballast fault of one or more DALI devices. |
Fault Converter | This item is only available for at least one DALI device that supports emergency lighting. If true, there is a converter fault of one or more DALI devices (not for Siemens N141/02). |
Fault Power Failure | True, if there is a power failure within the DALI gateway. |
Fault Short Circuit | True, if there is a general short cut on the DALI channel. |
...
Include Page Normal DALI testing server items per DALI gateway Normal DALI testing server items
For emergency DALI testing, the following Server Items are available under the sub tree "Emergency":
...
per DALI gateway
Include Page | ||||
---|---|---|---|---|
|
Info |
---|
Please keep in mind that these items will only appear when emergency testing is available for the gateway. For these KNX/DALI gateways at least one DALI device must support emergency lighting tests. This means that there must be a "Emergency Mapping Definition" for at least one DALI device. Note that emergency testing is only available for self contained battery lamps. |
...
For each configured DALI device, a sub tree with the name "Device<number>" is shown within the Server Item Tree. Each device has at least the following Server Items:
item name | description |
---|---|
Name | Human-readable name of the DALI device. The default name is "Device<number>". This name can be changed within the Device Name Mapping Definitions. |
Fault | True, if either a lamp or a device fault occurred. |
Fault Lamp | True, if there is a lamp fault. |
Fault Ballast | True, if there is a ballast fault. |
Fault Converter | (Emergency lighting only) True, if there is a converter faultfault (not for Siemens N141/02). |
Test succeeded | True, if a response is received during the test. |
If a device is also an emergency light (i.e. it has a valid emergency mapping definition), the following items are available in the sub tree "Emergency":
item name | description | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Test Running | True, when an emergency DALI test is currently running. | ||||||||||||||
Start Function Test | Used to trigger a function test for this device. | ||||||||||||||
Start Duration Test | Used to trigger a duration test for this device. | ||||||||||||||
Start Partial Duration Test | Used to trigger a partial duration test for this device. | ||||||||||||||
Start Battery Test | Used to trigger a battery test for this device. | ||||||||||||||
Stop Test | Used to stop a running test. | ||||||||||||||
Last test was | Shows the type of the last test.
| ||||||||||||||
Last test faulted | True, if there was no test result response. This may be the case when the DALI does not support emergency tests. | ||||||||||||||
Converter defect | True, if the converter is defect. | ||||||||||||||
Fault battery | True, if there is a battery fault. | ||||||||||||||
Battery defect | True, if the battery is defect. | ||||||||||||||
Fault emergency light | True, if there is an emergency light failure. | ||||||||||||||
Max time function test exceeded | True, if the maximum time for the function test exceeded. | ||||||||||||||
Max time duration test exceeded | True, if the maximum time for the duration exceeded. | ||||||||||||||
Function test failed | True, if the function test failed. | ||||||||||||||
Duration test failed | True, if the duration test failed. | ||||||||||||||
Test result | Test result: The raw data as received from the gateway. Time results have to be multiplied by 2 minutes; Battery charge status is from 0 to 255 and has to be converted to percentage. |
Include Page | ||||
---|---|---|---|---|
|