Configuration
...
Warning |
---|
The group object "Emergency Test Start" (#40 or #1154) has to be configured for "Yes, DGN/S1.16.1 format" within ETS. Otherwise the emergency lighting tests will not work. |
Info |
---|
The ABB DG/S x.64.1.1 gateway uses emergency test start and result objects for all devices on one channel – there are no individual objects for each emergency ballast. Therefore, there no entries within the Emergency Mapping Definitions are created. If the emergency configuration is enabled it will appear within the ABB DG/S x.64.1.1 gateway definition. |
Functional description
These KNX/DALI gateway types provide 1 or 2 DALI channels with up to 64 DALI devices. In addition to normal DALI testing, they support emergency lighting and extended tests for emergency lighting too.
...
item name | description |
---|---|
Test Running | True, when an emergency DALI test is currently running. |
Start Function Test | Used to trigger a function test for this device. |
Start Duration Test | Used to trigger a duration test for this device. |
Start Partial Duration Test | Used to trigger a partial duration test for this device. |
Start Battery Test | Used to trigger a battery test for this device. |
Stop Test | Used to stop a running test. |
Remaining Test Runtime | Remaining runtime in minutes for a triggered test. |
Last test was | Shows the type of the last test, according to LaMPS test type encoding. |
Last test faulted | True, if there was no test result response. This may be the case if the DALI device does not support emergency tests. |
Converter defect | True, if the converter is defect. |
Fault battery | True, if there is a battery fault. |
Battery defect | True, if the battery is defect. |
Fault emergency light | True, if there is an emergency light failure. |
Function test triggered but not executed | True, if a function test was triggered but not finished. |
Duration test triggered but not executed | True, if a Duration test was triggered but not finished. |
Function test failed | True, if the function test failed. |
Duration test failed | True, if the duration test failed. |
Test result | Test result: The raw data as received from the gateway. Time results have to be multiplied by 2 minutes; Battery charge status rannges from 0 to 255 and has to be converted to percentage. |
...