Logic to change a data point value based on a checkin/checkout check-in/check-out signal from e.g. Fidelio/Opera.

Description

Lange Beschreibung

Inputs

  • Datapoint_1 (ItemID): Beschreibung
  • Datapoint_2 (ItemID, optional): Beschreibung

Outputs

  • Output1: Beschreibung

Parameters

  • Parameters (Any, optional): Beschreibung

 This logic can be used to change a data point value based on a check-in/check-out signal (RoomChecked item) of Fidelio/Opera. A typical use case would be the change of the setpoint or mode of a climate control.

Inputs

  • CheckInOut (ItemID): here the "RoomChecked" Item of the specified room has to be selected (e.g. NETx\API\NXA_FIDELIO\HotelA\Floor1\101\RoomChecked)

Outputs

  • Output (ItemID): data point that shall be written.

Parameters

  • ValueCheckin (Any, optional): value that shall be written to the output when a check-in happens. If not specified, no value is written.
  • ValueCheckout (Any, optional): value that shall be written to the output when a check-out happens. If not specified, no value is written.
  • Delay(Number, optional): value that will delay the output. If not specified, no delay will happen. 

Possible trigger types

  • All

Available since:

NETx BMS Server 2.0