The NETx KNX IP Secure Router is designed for installation on a DIN rail with a width of 1 unit (18mm). It features the following controls and displays:

(error) TODO grafikImage Added

❶: KNX bus connector

❷: KNX programming LED

❸: KNX programming button

❹: KNX LED

❺: Mode LED

❻: IP LED

❼: Pass GAs button

❽: Pass IAs button

The NETx KNX IP Secure Router is powered by the KNX bus. An external power supply is not necessary.

...

The KNX LED ❹ lights up green if the device is successfully powered by the KNX bus. This LED indicates telegram traffic on the KNX bus by flickering. Communication failures (e.g. repetitions of telegrams or telegram fragments) are indicated by a short change of the LED color to
red. Overview of the different indications of the KNX LED ❹:

LED StatusMeaning
LED lights greenKNX bus voltage available
LED flickers greenTelegram traffic on the KNX bus
LED shortly redCommunication failures on the KNX bus

The IP LED ❻ lights up when an Ethernet link is active. This LED is green if the device has valid IP settings (IP address, Sub net and Gateway). With invalid or nonexistent IP settings the LED is red. This is also the case if e.g. the device has not yet received the IP settings by a DHCP server.

...

Overview of the different indications of the IP LED ❻:

LED StatusMeaning
LED lights greenThe device has an active Ethernet link and valid IP settings.
LED lights redThe device has an active Ethernet link and invalid IP settings or not yet received the IP settings by a DHCP server.
LED flickers greenIP telegram traffic

For testing purposes (for example, during commissioning) the configured routing settings (filter or block) can be bypassed via manual operation.

...

Overview of the different indications of the Mode LED ❺:

LED StatusMeaning
LED lights greenDevice is working in standard operation mode.
LED lights redProgramming mode is active
LED flashes 1x orangeProgramming mode is not active.
Manual operation is active.
Forwarding IA or GA
LED flashes 2x orangeProgramming mode is not active.
Manual operation is active.
Forwarding IA and GA
LED flashes redProgramming mode is not active.
Manual operation is not active.
The device is not properly loaded e.g. after an interrupted download.

Factory default settings

The following configuration is set by factory default:

...