Basic architecture
The NETx Server provides the opportunity to integrate hotel room status information from an Infor Hotel Management System (HMS).The interface is certified by Infor. The official certificate can be downloaded here.
The following figure shows how the integration has to be done.
The Infor HMS provides a standardized interface based on the SOAP protocol to establish a two-way communication between the NETx Server and the Infor HMS to synchronize the status of hotel rooms and receive updates such as check in, check out, and room move.
...
The NETx Server keeps track of the room status within the item tree.
Installation
The driver is implemented as a plugin for the NETx Server. Therefore, it has to be installed via the Extension Manager. To do so, stop the server and open the Extension Manager via the studio using the menu "Extensions". Select the "Infor" interface and press install as shown in the following screenshot:
...
After having installed the interface, restart the studio.
Integration steps
Determine local IP address to connect to the NETx Infor Endpoint
To determine the local IP address of the NETx Infor Endpoint, open a command prompt in Windows and enter "ipconfig".
To do so, press the Windows key and enter "cmd". Click the suggested Command Prompt app.
...
The NETx Infor endpoint can basically run on any port and path, but the recommended way is: http://<ip>/infor
In our case: http://192.168.0.5/infor
Configuration
Once the Infor plugin has been successfully installed, you should see a menu entry "Infor" within the menu "Modules".
To configure how to connect to the Infor HMS and vice versa, click the "Configuration ..." entry within "Modules" => "Infor".
Parameters (the yellow highlighted parameters are MANDATORY for the Infor Plugin to work properly)
Parameter | Description | Example | Note |
---|---|---|---|
NETx Infor endpoint | The NETx Server endpoint to listen for incoming requests from the Infor HMS | http://192.168.0.5/infor | Please see the "Determine local IP address" section below to see how you can determine the endpoint |
Infor HMS endpoint | The Infor HMS endpoint to send outgoing requests from the NETx Server. | http://192.168.0.6/netx | Please request this parameter from the Infor HMS operator and enter it accordingly |
Infor HMS Hotel Code | The identifier of the controlled hotel | HMS01 | Please request this parameter from the Infor HMS operator and enter it accordingly |
Request timeout | The request timeout in seconds | 60 | Optional |
Rooms
In order to know which rooms need be tracked, you have to provide some information regarding the room definitions.
You should be able to export this information from the Infor HMS and import it to the studio so that you don't have to enter it manually.
Please talk to the Infor HMS operator to learn how to get the required room information.
...
The retrieved information for each room from the Infor HMS is stored as a server item "RoomChecked" within the configured path.
Connecting to the NETx Infor endpoint from an external network
Please keep in mind , that the NETx Infor endpoint only listens to the specified IP address in the LOCAL network and is NOT publicly exposed to the internet.
If the Infor HMS is running in a separate network, you will need to set up some kind of p ort port forwarding in the network where the NETx Server is running, so that the endpoint can be reached from other networks.
...
The Public NETx endpoint needs to be properly configured within the network where the NETx Server is running.
The public endpoint will then redirect the traffic to the local IP address of the NETx Server.
Sample configuration: