Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

Within this configuration file, server settings for the OPC UA driver are configured.

Info
titleFile location

<WorkspaceDirectory>\ConfigFiles\xio.OPCUA.cfg

Within this configuration files, the server side of the OPC UA driver can be configured. The following configuration options are available:


parameterunitdescriptiondefaultEnable OPC UAtrue/false
1 - 65535
ParameterDescriptionScopeUnit

Default value

xio.OPCUA.Enabled

Enables/disables the OPC UA server interface.

true/false
Local TPC PortLocal HTTP Port
nonefalse
xio.OPCUA.LocalTCPPortPort of the local OPC UA TCP transport binding.
48400
1 - 65535TCP port48400
xio.OPCUA.LocalHTTPPortPort of the local OPC UA http transport binding.
48401Use BMS authentication backend (BMS Platform only)true/false
1 - 65535TCP port48401
xio.OPCUA.UseBmsAuthenticationOnly available for BMS Platform: If enabled, the BMS user authentication module is also used for OPC UAtrue
User nameIf true, all LaMPS items are marked as persistent and thus item values restored after server startup or after reconnecting the KNXnet/IP router or interface.PasswordIf true, all thresholds will be overridden by the values that are defined within the circuit definition.Enable Anonymous Accesstrue/falsefalse
/falsenonetrue
xio.OPCUA.UsernameIf BMS authentication is not enabled or NETx MP Server is used, the user for connecting to OPC UA has to be specified here. As an alternative, anonymous access can be enabled.stringnonenone
xio.OPCUA.PasswordIf BMS authentication is not enabled or NETx MP Server is used, the password for connecting to OPC UA has to be specified here. As an alternative, anonymous access can be enabled.stringnonenone
xio.OPCUA.AnonAccessIf enabled, no user name / password has to be specified for connecting to OPC UA (not recommended).true/falsenonefalse
xio.OPCUA.ApplicationCertificateLifeTimeCertificate lifetime (in months) for newly created certificates.1 - 65535months120
xio.OPCUA.ApplicationCertificatePathPath to the application certificate within the Windows certificate store.

LocalMachine\NETx BMS Platform
xio.OPCUA.ApplicationCertificateSubjectNameSubject name of application certificate.

NETx BMS Platform UA Wrapper
xio.OPCUA.TrustedPeerCertificatesPathPath to trusted peer certificates within the Windows certificate store.

LocalMachine\NETx BMS Platform
xio.OPCUA.TrustedIssuerCertificatesPathPath to trusted issuer certificates within the Windows certificate store.

LocalMachine\NETx BMS Platform