Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

Name

Description

Scope

Unit

Default

Notes

SYS.SendVirtualTelegrams

Enables or disables the sending of telegrams for KNX main group addresses above 15.

ON, OFF

None

OFF

SYS.MaxSizeOfTelegramLogFile

Specifies the maximum size of the KNX telegram log file. If the size is exceeded, new records overwrite oldest records.

1 -

0 deactivates the KNX telegram log file.

0 – 1000

MB

10

SYS.SpinTelegramFile

If enabled a new KNX telegram log file is created every day.

ON, OFF

None

ON

SYS.MaxTelegramFileAge

When the Core Studio connects to NETx Server, all KNX telegram log files older than the given number of days are deleted. This function is disabled if the parameter is missing or 0.

0

-

3650

days

0

Available since R2 Build 2064

SYS.MaxXEventFileBackups

Defines the number of XDB backups that shall be kept on hard disk. -1: keep forever, 0: no backup, >=1 number of backups to be kept.

0 – 1000

None

-1

Available since R2 Build 2069

SYS.EnableDeviceManager

Enables the physical KNX device management. ON - the physical device management is enabled OFF - the physical device management is disabled

ON, OFF

None

ON

SYS.OPCInterfaceEnabled

Enables the OPC Server.

ON, OFF

None

ON

SYS.GenerateRandomValues

If the server is running in simulation mode and this parameter is set to "ON", the server generates random values for all server items. ON - the server generates random values if the server is running OFF - The server does not generate random values

ON, OFF

None

ON

SYS.EnableOperationTime

The server will calculate the operation time in seconds of KNX datapoints that are of type EIS1. ON - the operation time calculation is enabled OFF - the operation time calculation is disabled

ON, OFF

None

OFF

SYS.CodePage

Defines the code page that is used within the NETx BMS Core Server. Value of 0 indicates to use the Windows system code page.

1

-

65535

None

0

Modifying this value is not recommended. From version 4.2.1020 on this parameter is therefore hidden.

SYS.LoggingLevel

System logging level for providing additional output to server logs

-65535

-

65535

None

0

SYS.SpinLogFile

ON - the system log file switches to a new file every day. OFF - the system log file remains in the same file as long as the server is running.

ON, OFF

None

OFF

(warning) deprecated

SYS.MaxLogFilesAge

When the Core Studio connects to NETx Server, all system log files older than the given number of days are deleted. This function is disabled if the parameter is missing or 0.

0

-

3650

days

0

Available since R2 Build 2064

SYS.OPCBridgeStartDelay

Delay (in seconds) for connecting to the configured OPC DA server for clustering

0

-

600

seconds

10

Available since R2 Build 2010

SYS.ClusterSetUncertainOnDisconnect

If enabled, all items are reset if cluster server disconnects.

ON, OFF

None

OFF

SYS.PersistentValueTransactionInterval

Transaction interval for persistent values

0

-

60

seconds

1

Available since R2 Build 2060

SYS.GeoLatitude

Specifies the geographic latitude in degrees (+ is used for north, - for south)

0

-

360

90 – 90

degrees

0

SYS.GeoLongitude

Specifies the geographic longitude in degrees (+ is used for east, - for west)

0

-

360

180 – 180

degrees

0

SYS.GeoElevation

Specifies the geographic elevation in meters.

0

-500 – 10000

m

0

SYS.SunriseOffset

Sunrise offset time for calculated sun value item 'IsSunTime' (in minutes).

0

-360 – 360

min

0

SYS.SunsetOffset

Sunset offset time for calculated sun value item 'IsSunTime' (in minutes).

0

-360 – 360

min

0

SYS.SunTimeRandom

Random offset time for calculated sun value item 'IsSunTime' (in minutes).

0

-360 – 360

min

0

SYS.GatewayConnectionTimeout

Specifies the timeout value for availability check of the connected KNXnet/IP routers.

10

-

10000

ms

500

(warning) deprecated

SYS.GatewayConnectionTimeoutAttemptCount

Specifies the number of call attempts for the availability check of the connection of the connected KNXnet/IP routers in the case of an interruption.

1

-

10

None

3

(warning) deprecated


Article applies to the following products:

...