Name | Description | Scope | Unit | Default | Notes | |
---|---|---|---|---|---|---|
SYS.SendVirtualTelegrams | Enables or disables the sending of telegrams for KNX main group addresses above 15. | ON, OFF | None | OFF | ||
SYS.MaxSizeOfTelegramLogFile | Specifies the maximum size of the KNX telegram log file. If the size is exceeded, new records overwrite oldest records. 0 deactivates the KNX telegram log file. |
0 – 1000 | MB | 10 | ||||
SYS.SpinTelegramFile | If enabled a new KNX telegram log file is created every day. | ON, OFF | None | ON | ||
SYS.MaxTelegramFileAge | When the Core Studio connects to NETx Server, all KNX telegram log files older than the given number of days are deleted. This function is disabled if the parameter is missing or 0. | 0 – 3650 | days | 0 | Available since R2 Build 2064 | |
SYS.MaxXEventFileBackups | Defines the number of XDB backups that shall be kept on hard disk. -1: keep forever, 0: no backup, >=1 number of backups to be kept. | 0 – 1000 | None | -1 | Available since R2 Build 2069 | |
SYS.EnableDeviceManager | Enables the physical KNX device management. ON - the physical device management is enabled OFF - the physical device management is disabled | ON, OFF | None | ON | ||
SYS.OPCInterfaceEnabled | Enables the OPC Server. | ON, OFF | None | ON | ||
SYS.GenerateRandomValues | If the server is running in simulation mode and this parameter is set to "ON", the server generates random values for all server items. ON - the server generates random values if the server is running OFF - The server does not generate random values | ON, OFF | None | ON | ||
SYS.EnableOperationTime | The server will calculate the operation time in seconds of KNX datapoints that are of type EIS1. ON - the operation time calculation is enabled OFF - the operation time calculation is disabled | ON, OFF | None | OFF | ||
SYS.CodePage | Defines the code page that is used within the NETx BMS Core Server. Value of 0 indicates to use the Windows system code page. | 1 – 65535 | None | 0 | Modifying this value is not recommended. From version 4.2.1020 on this parameter is therefore hidden. | |
SYS.LoggingLevel | System logging level for providing additional output to server logs | -65535 – 65535 | None | 0 | ||
SYS.SpinLogFile | ON - the system log file switches to a new file every day. OFF - the system log file remains in the same file as long as the server is running. | ON, OFF | None | OFF | deprecated | |
SYS.MaxLogFilesAge | When the Core Studio connects to NETx Server, all system log files older than the given number of days are deleted. This function is disabled if the parameter is missing or 0. | 0 – 3650 | days | 0 | Available since R2 Build 2064 | |
SYS.OPCBridgeStartDelay | Delay (in seconds) for connecting to the configured OPC DA server for clustering | 0 – 600 | seconds | 10 | Available since R2 Build 2010 | |
SYS.ClusterSetUncertainOnDisconnect | If enabled, all items are reset if cluster server disconnects. | ON, OFF | None | OFF | ||
SYS.PersistentValueTransactionInterval | Transaction interval for persistent values | 0 – 60 | seconds | 1 | Available since R2 Build 2060 | |
SYS.GeoLatitude | Specifies the geographic latitude in degrees (+ is used for north, - for south) | -90 – 90 | degrees | 0 | ||
SYS.GeoLongitude | Specifies the geographic longitude in degrees (+ is used for east, - for west) | -180 – 180 | degrees | 0 | ||
SYS.GeoElevation | Specifies the geographic elevation in meters. | -500 – 10000 | m | 0 | ||
SYS.SunriseOffset | Sunrise offset time for calculated sun value item 'IsSunTime' (in minutes). | -360 – 360 | min | 0 | ||
SYS.SunsetOffset | Sunset offset time for calculated sun value item 'IsSunTime' (in minutes). | -360 – 360 | min | 0 | ||
SYS.SunTimeRandom | Random offset time for calculated sun value item 'IsSunTime' (in minutes). | -360 – 360 | min | 0 | ||
SYS.GatewayConnectionTimeout | Specifies the timeout value for availability check of the connected KNXnet/IP routers. | 10 – 10000 | ms | 500 | deprecated | |
SYS.GatewayConnectionTimeoutAttemptCount | Specifies the number of call attempts for the availability check of the connection of the connected KNXnet/IP routers in the case of an interruption. | 1 – 10 | None | 3 | deprecated |
Article applies to the following products:
...