Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

Within this configuration file, general settings for the Fidelio

...

/Opera interface are configured.

Info
titleFile location

<WorkspaceDirectory>\ConfigFiles\

...

nxapiFidelio.cfg

...


  • FIDELIO
  • SYS

FIDELIO-Parameters

 

Parameter
ParameterDescriptionScopeUnit

Default value

FIDELIO.IPAddress

Description

This defines
Specifies the IP address of the
FIDELIO or OPERA Unit
Fidelio/Opera server.

Scope

###.###.###.

IP addressNone

Default value

None
Parameter
FIDELIO.Port

Description

This defines
Specifies the TCP port number of the
FIDELIO or OPERA
Fidelio/Opera server.

Scope

### (
1-65535
)Unit

Parameter

None

Default value

5018

5003
FIDELIO.
Logging

Description

This enables the logging of the data telegrams from the FIDELIO or OPERA server.

Scope

ON/OFF

Unit

None

Default value

ON

Parameter

FIDELIO.LRC

Description

This turns on or off LRC for the data telegrams.

Scope

ON/OFF

Unit

None

Default value

OFF

Parameter

FIDELIO.UpdateOnReconnect

Description

If set data from FIDELIO or OPERA server are called to update the information inside the NETx BMS Core Server when the connection to the FIDELIO or OPERA server is reestablished.

Scope

ON/OFF

Unit

None

Default value

OFF

 

SYSTEM-Parameters

...

Parameter

...

SYS.RefreshInterval

...

Description

...

This defines the time between one call for data and the next one to the FIDELIO or OPERA server.

...

Scope

...

###

...

Unit

...

seconds

...

Default value

...

20

 

 

...

LRCTurns LRC for data telegrams on or off.ON/OFFNoneOFF
SYS.RefreshIntervalDefines the time between two calls for data to the Fidelio/Opera server.numericseconds20
FIDELIO.LoggingEnables logging of data telegrams to and from the Fidelio/Opera server.ON/OFFNoneOFF
FIDELIO.UpdateOnReconnectIf set, when the connection to the Fidelio/Opera server is (re-)established data from Fidelio/Opera server are queried to update the information in the NETx BMS Core Server.ON/OFFNone

ON

FIDELIO.UseControlByteEnables the acknowledged transmission of data telegrams.ON/OFFNoneOFF
FIDELIO.UseGCEnables or disables the use of "Guest Change (GC)" records.ON/OFFNone

ON

FIDELIO.UseLinkCheckIf enabled, the BMS server sends an "LS" record for keep alive checking in a cyclic interval. The interval can be defined by FIDELIO.AliveInterval.ON/OFFNoneOFF
FIDELIO.UseLALinkCheckUse "LA" keep alive checking;T;If enabled, the BMS server sends an "LA" record for keep alive checking in a cyclic interval. The interval can be defined by FIDELIO.AliveInterval.ON/OFFNone

ON

FIDELIO.AliveIntervalSpecifies the interval in seconds for keep alive checking.1 - 65535seconds300
FIDELIO.CommandTimeoutSpecifies command timeout in seconds used for start up and acknowledged transmission.1 - 65535seconds3
FIDELIO.MessagesEnabledIf enabled, messages to and from Fidelio/Opera can be sent or received.ON/OFFNone

ON

FIDELIO.RoomStatusEnabledIf enabled, it is request to use RE (room equipment) records.ON/OFFNone

ON

FIDELIO.UsedGIRecordsSpecifies which optional fields shall be sent by Fidelio/Opera within GI records. Use <NONE> if no additional optional fields shall be sent.stringNoneGAGDGFGLGNGTGVNPSFDATI
FIDELIO.UsedGCRecordsSpecifies which optional fields shall be sent by Fidelio/Opera within GC records. Use <NONE> if no additional optional fields shall be sent.stringNoneROGAGDGFGLGNGTGVNPDATI
FIDELIO.UsedGORecordsSpecifies which optional fields shall be sent by Fidelio/Opera within GO records. Use <NONE> if no additional optional fields shall be sent.stringNoneSFDATI
FIDELIO.UsedRERecordsSpecifies which optional fields shall be sent by Fidelio/Opera within RE records. Use <NONE> if no additional optional fields shall be sent.stringNoneG#CSDNRSCTVMPPML
SYS.SihotExtensionEnable Sihot extension.ON/OFFNoneOFF