The configuration of the web visualization settings is done in the respective configuration file.
Info | |
---|---|
title | File location<WorkspaceDirectory>\ConfigFiles\xio.WebVisu.cfg |
Parameter | Description | Scope | Unit | Default value |
---|---|---|---|---|
Web.Notification.AlarmLevel | Level for alarm notification pop-ups. | Warning, Error, Info | None | Warning |
Web.Notification.AlarmAutoClose | If enabled, alarm notification pop ups are closed after the above configured time out. | ON, OFF | None | ON |
Web.Notification.AlarmTimeOut | Timeout for alarm notification pop ups if enabled. | 1 – 1000000 | ms | 10000 |
Web.LoginMode | Specifies the behavior when a user connects but the connection limit is reached. Block means that the user cannot proceed. Force means that the user can select a connection which will be dropped. | Force, Block | None | Force |
Web.LoginTitle | Title that is shown at the login page of the web visualization. | String | None | NETx BMS Visualization |
Web.LoginLogoFile | Logo file which is shown at login page. | String | None | /server/resources/images/favicon.ico |
Web.AllowZooming | If enabled, the zooming feature of web browser can be used. | ON, OFF | None | OFF |
Web.MaxLoadingClients | Number of clients that are allowed to connect at the same time. | 1 – 1000 | None | 4 |
Web.ClientBorderSpace | Number of pixels used as visualization page padding. | 0 – 100 | px | 0 |
Web.ShowTooltipOnTouch | If enabled, tooltips are shown on touch devices. | ON, OFF | None | OFF |
Web.ClientTimeout | Specify the inactivity client timeout in seconds. If the client is not active after this timeout, it will be disconnected and logged out by the server. | 30 - 86400 | s | 180 |
Web.BoolVariableConversionToNumber | If enabled, boolean values (true / false) of variable values will be converted to 1 / 0. Only for backward compatibility - do not enable this option for new projects. | ON, OFF | None | OFF |
Applies to the following products
NETx BMS Platform