(question)TODO: Still exist ?? YES

Location:

<WorkspaceDirectory>\DataFiles\nxaKNXObjectDefinitions.dat


Info

! This definition file can also be generated using the ETS app import wizard (Studio → KNX → Inport NETx ETS App file ...) which generates the ETS object definitions from an exported ETS project.


Within this configuration file, the KNX communication objects as represented in the item tree are specified. The structure of the definition file is as follows:


'Syntax of the ETS Object Definition Table:
'Name;Object function;Device name;Path;Communication flag;Read flag;Write flag;Transmit flag;Update flag;Read on init flag;Physical address;IP address;Group addresses (first one is sending)
Output A;10: Switch;Room1 - Light HVAC Actuator;Demo_Case_Large\Buildings\BuildingA\Floor1\Cabinet1\3.1.1;T;F;T;F;F;F ;3.1.1;192.168.1.15;0/0/1@192.168.1.15
Output A;29: Status Switch;Room1 - Light HVAC Actuator;Demo_Case_Large\Buildings\BuildingA\Floor1\Cabinet1\3.1.1;T;T;F ;T;F;F;3.1.1;192.168.1.15;0/0/2@192.168.1.15
Output B;30: Switch;Room1 - Light HVAC Actuator;Demo_Case_Large\Buildings\BuildingA\Floor1\Cabinet1\3.1.1;T;F;T;F;F;F ;3.1.1;192.168.1.15;0/0/3@192.168.1.15
Output B;49: Status Switch;Room1 - Light HVAC Actuator;Demo_Case_Large\Buildings\BuildingA\Floor1\Cabinet1\3.1.1;T;T;F ;T;F;F;3.1.1;192.168.1.15;0/0/4@192.168.1.15
Each line – except comment lines that start with ' – defines a single communication object.
! The ETS object definitions within this file are automatically created by the NETx BMS App. Therefore, editing it manually is not necessary in general.

 

...






   1Name 
This parameter refers to the name of the communication object.
2Object function 
Here the name of the function of the communication object is specified.
3Device name 
This is the device name to which the communication object belongs to.
4Path 
This column defines the path within the ETS view where the communication object is shown.
5Communication flag 
The KNX communication flag of the communication object. For more information see ETS documentation.
6Read flag 
The KNX read flag of the communication object. For more information see ETS documentation.
7Write flag 
The KNX write flag of the communication object. For more information see ETS documentation.
8Transmit flag 
The KNX transmit flag of the communication object. For more information see ETS documentation.
9Update flag 
The KNX update flag of the communication object. For more information see ETS documentation.
10Read on init flag 
The KNX read on init flag of the communication object. For more information see ETS documentation.
11Physical address 
The physical address of the device where the communication object is located.
12Reserved 
Not used.
13Group addresses (first one is sending) 
The KNX group addresses that are linked to the communication object. The first group address is the sending group address i.e. the address which is used for send whenever the communication object changes its value.

 

...