Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

The interface configuration can be edited in the NETx Core Server Studio at Modules > Qlite> Interface Definitions

...

Col#

Parameter

Description

Scope

Unit

Default value

1

Name

Name of the interface. Must be unique.

string

None


2

IP address

IP address of the QL-NE100 device.

IP-Address

None


3

Port

UDP port of the QL-NE100 device.

Port number

None

57277

4

Send interval

Time delay between sending two messages.

integer

ms

200

5

Log messages

If set to true, all received and sent messages are logged inĀ <WorkspaceDirectory>\LogFiles\nxaQlite-<InterfaceName>_<Datecode>.log

boolean

None

False

6

Ping after

Start pinging the interface after not receiving packets for this time period.

integer

s

50

7

Ping interval

Time between sending pings to the interface.

integer

s

10

8

Ping retries

Connection to the interface is considered lost after this amount of failed pings.

integer

None

2

9

Channel Ranges

Defines the channels that shall be available as server items. It is possible to define comma separated list that also contains ranges. E.g. 1-10,15,250-310. If left empty, no channels are available.

integer list

1 - 512

None

10

Show Service Items

If set to true, five service items will be shown for each interface.

boolean

None

False

Send interval

The NETx Server has to request the current values of all devices on startup. This means a lot of requests will be sent at the same time. In order to avoid overloading of the bus, these messages are queued.

...

  • Key Card Inserted

  • Key Card Off

  • Do Not DisturbeDisturb

  • Make Up Room

  • Laundry

This These items are read only.