Configuration

...

parametertypeoptional/mandatorycommunication objectdescriptiondefault
Fault LampsItemIdMKNX Object #17, polledTrue, if there is a lamp error for at least 1 DALI device.
Fault BallastItemIdMKNX Object #18, polledTrue, if there is a ballast error for at least 1 DALI device.
Fault DALIItemIdOKNX Object #19, polledTrue, if there is a general DALI error.
Diagnostics ItemIdMKNX Object #25#20Used to trigger a normal DALI request and to get the test result.
Emergency Test StartItemIdOKNX Object #31Used to trigger an emergency DALI test for a dedicated device.
Emergency Test ResultItemIdOKNX Object #33Used to get the result of an emergency DALI test.
Emergency Mode ActiveItemIdOKNX Object #35True, if the DALI emergency lighting mode is active.
Emergency Test IntervalintO
Specifies how long the driver will wait between sending two emergency start requests.10 s


Info

The ABB DGN/S 1.16.1 gateway uses emergency test start and result objects for all devices on one channel – there are no individual objects for each emergency ballast as it is for other gateways. Therefore, there will appear no entry within the Emergency Mapping Definitions. If the emergency configuration is enabled it will appear within the ABB DGN/S 1.16.1 gateway definition.

Functional Description

These KNX/DALI gateway types provide 1 with up to 64 DALI devices. In addition to normal DALI testing, they support emergency lighting and extended tests for emergency lighting too.

...

Include Page
Normal DALI testing server items per DALI gateway
Normal DALI testing server items
For emergency DALI testing, the following Server Items
per DALI gateway

Include Page
Emergency testing server items per DALI gateway
Emergency testing server items per DALI gateway

In addition, the following device-specific items are available under the sub tree "Emergency":

item namedescription
Emergency Lights On/Off
Start Function TestUsed to trigger a function test for all emergency DALI lights.Start Partial Duration TestUsed to trigger a partial duration test for all emergency DALI lights.Start Duration TestUsed to trigger a duration test for all emergency DALI lights.Start Battery TestUsed to trigger a battery test for all emergency DALI lights.Stop TestUsed to stop a running test.Emergency Lights test running
True
, if an emergency DALI test
if the emergency mode is currently
running
active within the gateway.


Info

Please keep in mind that these items will only appear when emergency testing is available for the gateway. For these KNX/DALI gateways the "Emergency Test Start (#32, #40 or #1154)" and "Emergency Test Result (#33, #42 or #1156)" objects must be available and configured in order to support emergency testing. Note that emergency testing is only available for self contained battery lamps.

...

item namedescription
Test RunningTrue, when an emergency DALI test is currently running.
Start Function TestUsed to trigger a function test for this device.
Start Duration TestUsed to trigger a duration test for this device.
Start Partial Duration TestUsed to trigger a partial duration test for this device.
Start Battery TestUsed to trigger a battery test for this device.
Stop TestUsed to stop a running test.
Remaining Test Runtime

Remaining runtime in minutes for a triggered test.

Last test was

Shows the type of the last test. 

valuedescription
0"No Test"
1"Function Test"
2"Partial duration test"
3"Duration test"
4"Battery test"
255"Test not supported"


Last test faultedTrue, if there was no test result response. This may be the case when the DALI does not support emergency tests.
Converter defectTrue, if the converter is defect.
Fault batteryTrue, if there is a battery fault.
Battery defectTrue, if the battery is defect.
Fault emergency lightTrue, if there is an emergency light failure.
Function test triggered but not executedTrue, if a function test was triggered but not finished.
Duration test triggered but not executedTrue, if a Duration test was triggered but not finished.
Function test failedTrue, if the function test failed.
Duration test failedTrue, if the duration test failed.
Test resultTest result: The raw data as received from the gateway. Time results have to be multiplied by 2 minutes; Battery charge status is from 0 to 255 and has to be converted to percentage.

Include Page
Specific emergency test result Emergency testing server items per DALI device / results per test typeSpecific emergency test result items
Emergency testing server items per DALI device / results per test type