For emergency DALI testing, the following Server Items are available under the sub tree "Emergency":

item name

description

Start Function TestUsed to trigger a function test for all emergency DALI lights.
Start Partial Duration TestUsed to trigger a partial duration test for all emergency DALI lights.
Start Duration TestUsed to trigger a duration test for all emergency DALI lights.
Start Battery TestUsed to trigger a battery test for all emergency DALI lights.
Stop TestUsed to stop a running test.
Test RunningTrue, if an emergency DALI test is currently running.
FaultTrue, if an emergency test of at least 1 DALI light failed.
Last test faultedTrue, if "Last test faulted" of at least 1 DALI light is currently true.
Converter defectTrue, if "Converter defect" of at least 1 DALI light is currently true.
Battery fault or defectTrue, if "Battery fault or defect" of at least 1 DALI light is currently true.
Fault emergency lightTrue, if "Fault emergency light" of at least 1 DALI light is currently true.