For normal DALI testing, the following server items are available:

item name

access

description

Trigger faulty devices only

RW

If true then the next test will test only devices that are mentioned in the Faulty devices server item. Otherwise all devices are tested.

Trigger Test

W

Used to trigger a normal DALI test for all devices.

Test Running

R

True, when a normal DALI test is currently running.

Number Faulty Devices

R

Number of faulty devices as determined in the last test execution.

Faulty devices

R

A comma-separated sorted list of numbers of faulty DALI devices.