<table class="wrapped"> <colgroup> <col/> <col/> </colgroup> <tbody> <tr> <th> <p>
<em>Parameter</em> </p> </th> <th> <p>SYS.Historizing</p> </th> </tr> <tr> <td> <p> <em>Description</em> </p> </td> <td> <p> Enables or disables the storing of historical values into the SQL database. </p> </td> </tr> <tr> <td> <p> <em>Scope</em> </p>
</td> <td> <p>ON, OFF</p> </td> </tr> <tr> <td> <p> <em>Unit</em> </p> </td> <td>
<p> None </p> </td> </tr> <tr> <td> <p> <em>Default value</em> </p> </td> <td> <p> ON </p> </td> </tr> </tbody> </table> <p></p>
<table class="wrapped"> <colgroup> <col/> <col/> </colgroup> <tbody> <tr> <th> <p>
<em>Parameter</em> </p> </th> <th> <p>SYS.BackupHistorizing</p> </th> </tr> <tr> <td> <p> <em>Description</em> </p> </td> <td> <p> If enabled, the backup server also stores historical values in the historical database even if the backup server is inactive. </p> </td> </tr> <tr> <td> <p> <em>Scope</em> </p> </td> <td> <p>ON, OFF</p>
</td> </tr> <tr> <td> <p> <em>Unit</em> </p> </td> <td> <p> None </p> </td> </tr>
<tr> <td> <p> <em>Default value</em> </p> </td> <td> <p> OFF </p> </td> </tr> </tbody>
</table> <p></p>
<table class="wrapped"> <colgroup> <col/> <col/> </colgroup> <tbody> <tr> <th> <p>
<em>Parameter</em> </p> </th> <th> <p>SYS.UseTelegramDataFile</p> </th> </tr> <tr> <td> <p> <em>Description</em> </p> </td> <td> <p> It specifies whether a virtual image of the plant (i.e. the values of all defined datapoints) is written to disk.</p>
</td> </tr> <tr> <td> <p> <em>Scope</em> </p> </td> <td> <p>ON, OFF</p> </td> </tr>
<tr> <td> <p> <em>Unit</em> </p> </td> <td> <p> None </p> </td> </tr> <tr> <td> <p>
<em>Default value</em> </p> </td> <td> <p> ON </p> </td> </tr> </tbody> </table> <p></p>
<table class="wrapped"> <colgroup> <col/> <col/> </colgroup> <tbody> <tr> <th> <p> <em>Parameter</em> </p> </th> <th> <p>SYS.SendVirtualTelegrams</p> </th> </tr> <tr> <td> <p> <em>Description</em> </p> </td> <td> <p> Enables or disables the sending of telegrams for KNX main group addresses above 15.</p> </td> </tr> <tr> <td> <p>
<em>Scope</em> </p> </td> <td> <p>ON, OFF</p> </td> </tr> <tr> <td> <p> <em>Unit</em>
</p> </td> <td> <p> None </p> </td> </tr> <tr> <td> <p> <em>Default value</em> </p>
</td> <td> <p> OFF </p> </td> </tr> </tbody> </table> <p></p>
<table class="wrapped"> <colgroup> <col/> <col/> </colgroup> <tbody> <tr> <th> <p>
<em>Parameter</em> </p> </th> <th> <p>SYS.MaxSizeOfTelegramLogFile</p> </th> </tr> <tr> <td> <p> <em>Description</em> </p> </td> <td> <p> It specifies the maximum size of the telegram log file. </p> </td> </tr> <tr> <td> <p> <em>Scope</em> </p> </td> <td> <p>1 - 1000</p> </td> </tr> <tr> <td> <p> <em>Unit</em> </p> </td> <td> <p>
Megabyte </p> </td> </tr> <tr> <td> <p> <em>Default value</em> </p> </td> <td> <p>
10 </p> </td> </tr> </tbody> </table> <p></p>
<table class="wrapped"> <colgroup> <col/> <col/> </colgroup> <tbody> <tr> <th> <p>
<em>Parameter</em> </p> </th> <th> <p>SYS.EnableDeviceManager</p> </th> </tr> <tr> <td> <p> <em>Description</em> </p> </td> <td> <p> This parameter enables the physical KNX device management.
ON - the physical device management is enabled
OFF - the physical device management is disabled</p> </td> </tr> <tr> <td> <p> <em>Scope</em>
</p> </td> <td> <p>ON, OFF</p> </td> </tr> <tr> <td> <p> <em>Unit</em> </p> </td>
<td> <p> None </p> </td> </tr> <tr> <td> <p> <em>Default value</em> </p> </td> <td>
<p> ON </p> </td> </tr> </tbody> </table> <p></p>
<table class="wrapped"> <colgroup> <col/> <col/> </colgroup> <tbody> <tr> <th> <p>
<em>Parameter</em> </p> </th> <th> <p>SYS.GenerateRandomValues</p> </th> </tr> <tr> <td> <p> <em>Description</em> </p> </td> <td> <p> If the server is running in simulation mode and this parameter is set to "ON", the server generates random values for all server items.
ON - the server generates random values if the server is running
OFF - The server does not generate random values </p> </td> </tr> <tr> <td> <p> <em>Scope</em>
</p> </td> <td> <p>ON, OFF</p> </td> </tr> <tr> <td> <p> <em>Unit</em> </p> </td>
<td> <p> None </p> </td> </tr> <tr> <td> <p> <em>Default value</em> </p> </td> <td>
<p> ON </p> </td> </tr> </tbody> </table> <p></p>
<table class="wrapped"> <colgroup> <col/> <col/> </colgroup> <tbody> <tr> <th> <p>
<em>Parameter</em> </p> </th> <th> <p>SYS.EnableOperationTime</p> </th> </tr> <tr> <td> <p> <em>Description</em> </p> </td> <td> <p> The server will calculate the operation time in seconds of KNX datapoints that are of type EIS1.
ON - the operation time calculation is enabled
OFF - the operation time calculation is disabled</p> </td> </tr> <tr> <td> <p> <em>Scope</em>
</p> </td> <td> <p>ON, OFF</p> </td> </tr> <tr> <td> <p> <em>Unit</em> </p> </td>
<td> <p> None </p> </td> </tr> <tr> <td> <p> <em>Default value</em> </p> </td> <td>
<p> OFF </p> </td> </tr> </tbody> </table> <p></p>
<table class="wrapped"> <colgroup> <col/> <col/> </colgroup> <tbody> <tr> <th> <p>
<em>Parameter</em> </p> </th> <th> <p>SYS.GeoLatitude</p> </th> </tr> <tr> <td> <p> <em>Description</em> </p> </td> <td> <p> This parameter specifies the geographic latitude in degrees (+ is used for north, - for south)</p> </td> </tr> <tr> <td>
<p> <em>Scope</em> </p> </td> <td> <p>0 - 360</p> </td> </tr> <tr> <td> <p> <em>Unit</em>
</p> </td> <td> <p> degrees </p> </td> </tr> <tr> <td> <p> <em>Default value</em>
</p> </td> <td> <p> 0 </p> </td> </tr> </tbody> </table> <p></p>
<table class="wrapped"> <colgroup> <col/> <col/> </colgroup> <tbody> <tr> <th> <p>
<em>Parameter</em> </p> </th> <th> <p>SYS.GeoLongitude</p> </th> </tr> <tr> <td> <p> <em>Description</em> </p> </td> <td> <p> This parameter specifies the geographic longitude in degrees (+ is used for east, - for west)</p> </td> </tr> <tr> <td> <p>
<em>Scope</em> </p> </td> <td> <p>0 - 360</p> </td> </tr> <tr> <td> <p> <em>Unit</em>
</p> </td> <td> <p> degrees </p> </td> </tr> <tr> <td> <p> <em>Default value</em>
</p> </td> <td> <p> 0 </p> </td> </tr> </tbody> </table> <p></p>
<table class="wrapped"> <colgroup> <col/> <col/> </colgroup> <tbody> <tr> <th> <p>
<em>Parameter</em> </p> </th> <th> <p>SYS.GeoElevation</p> </th> </tr> <tr> <td> <p> <em>Description</em> </p> </td> <td> <p> It specifies the geographic elevation in meters.</p> </td> </tr> <tr> <td> <p> <em>Scope</em> </p> </td> <td> <p>0 - 10000</p>
</td> </tr> <tr> <td> <p> <em>Unit</em> </p> </td> <td> <p> meters </p> </td> </tr>
<tr> <td> <p> <em>Default value</em> </p> </td> <td> <p> 0 </p> </td> </tr> </tbody> </table> <p></p>
! Following SYSTEM parameters are available only for compatibility reasons. In future versions they may vanish.
<table class="wrapped"> <colgroup> <col/> <col/> </colgroup> <tbody> <tr> <th> <p>
<em>Parameter</em> </p> </th> <th> <p>SYS.GatewayConnectionTimeout</p> </th> </tr> <tr> <td> <p> <em>Description</em> </p> </td> <td> <p> It specifies the timeout value for availability check of the connected KNXnet/IP routers.</p> </td> </tr> <tr> <td>
<p> <em>Scope</em> </p> </td> <td> <p>10 - 10000</p> </td> </tr> <tr> <td> <p> <em>Unit</em>
</p> </td> <td> <p> milliseconds </p> </td> </tr> <tr> <td> <p> <em>Default value</em>
</p> </td> <td> <p> 500 </p> </td> </tr> </tbody> </table> <p></p>
<table class="wrapped"> <colgroup> <col/> <col/> </colgroup> <tbody> <tr> <th> <p>
<em>Parameter</em> </p> </th> <th> <p>SYS.GatewayConnectionTimeoutAttemptCount</p> </th> </tr> <tr> <td> <p> <em>Description</em> </p> </td> <td> <p> It specifies the number of call attempts for the availability check of the connection of the connected KNXnet/IP routers in the case of an interruption.</p> </td> </tr> <tr> <td> <p> <em>Scope</em>
</p> </td> <td> <p>1 - 10</p> </td> </tr> <tr> <td> <p> <em>Unit</em> </p> </td>
<td> <p> None </p> </td> </tr> <tr> <td> <p> <em>Default value</em> </p> </td> <td>
<p> 3 </p> </td> </tr> </tbody> </table> <p></p>
<table class="wrapped"> <colgroup> <col/> <col/> </colgroup> <tbody> <tr> <th> <p>
<em>Parameter</em> </p> </th> <th> <p>SYS.CodePage</p> </th> </tr> <tr> <td> <p> <em>Description</em> </p> </td> <td> <p> Defines the code page that is used within the NETx BMS Core Server.</p> </td> </tr> <tr> <td> <p> <em>Scope</em> </p> </td>
<td> <p></p> </td> </tr> <tr> <td> <p> <em>Unit</em> </p> </td> <td> <p> None </p>
</td> </tr> <tr> <td> <p> <em>Default value</em> </p> </td> <td> <p> 1250 </p> </td>
</tr> </tbody> </table> <p></p>
<table class="wrapped"> <colgroup> <col/> <col/> </colgroup> <tbody> <tr> <th> <p>
<em>Parameter</em> </p> </th> <th> <p>SYS.SpinLogFile</p> </th> </tr> <tr> <td> <p> <em>Description</em> </p> </td> <td> <p> ON - the system log file switches to a new file every day.
OFF - the system log file remains in the same file as long as the server is running.
</p> </td> </tr> <tr> <td> <p> <em>Scope</em> </p> </td> <td> <p>ON, OFF</p> </td>
</tr> <tr> <td> <p> <em>Unit</em> </p> </td> <td> <p> None </p> </td> </tr> <tr>
<td> <p> <em>Default value</em> </p> </td> <td> <p> OFF </p> </td> </tr> </tbody>
</table> <p></p>