The NETx BMS Core Server supports all KNX datapoint types (DPT) as defined in the KNX Standard 2.1 in Section 3.7.2. In addition, the EIS types are also supported.
Table 4.2.: KNX EIS data types

Data size

EIS Type

(S)igned /
(U)nsigned

Unit

Description

1BIT

EIS1

 

 

Switch

4BIT

EIS2

 

 

Dim object
Bit 0=Up/Down Bit 1..3=Speed if Bit1..4=0 Stop

3BYTE

EIS3

 

 

Time

3BYTE

EIS4

 

 

Date( Attention: century 2-digits)

2BYTE

EIS5

 

°C

Temperature

2BYTE

EIS5

 

K

Temperature difference

2BYTE

EIS5

 

K/h

Temperature gradient

2BYTE

EIS5

 

Lux

Light intensity

2BYTE

EIS5

 

m/s

Wind velocity

2BYTE

EIS5

 

Pa

Air pressure

 

Table 4.2.: KNX EIS data types

Data size

EIS Type

(S)igned /
(U)nsigned

Unit

Description

2BYTE

EIS5

 

s

Time difference

2BYTE

EIS5

 

ms

Time difference

2BYTE

EIS5

 

mV

Voltage

2BYTE

EIS5

 

mA

Current

1BYTE

EIS6

 

%

Relative Luminance (0...100)

1BYTE

EIS6

 

%

Relative Humidity (0...100)

1BYTE

EIS6

 

°

Wind direction (0...360)

1BYTE

EIS6

U

 

8-Bit unsigned (unofficial Type)

1BYTE

EIS6

S

 

8-Bit signed (unofficial Type)

1BIT

EIS7

 

 

Motor Motion

2BIT

EIS8

 

 

Priority Control

4BYTE

EIS9

 

m/s2

Acceleration

4BYTE

EIS9

 

rad/s2

 

4BYTE

EIS9

 

J/mol

 

4BYTE

EIS9

 

1/s

 

4BYTE

EIS9

 

mol

 

4BYTE

EIS9

 

 

 

4BYTE

EIS9

 

rad

 

4BYTE

EIS9

 

°

 

4BYTE

EIS9

 

Js

 

4BYTE

EIS9

 

rad/s

 

4BYTE

EIS9

 

m2

 

4BYTE

EIS9

 

F

 

4BYTE

EIS9

 

C/m2

 

4BYTE

EIS9

 

C/m3

 

4BYTE

EIS9

 

m2/N

 

4BYTE

EIS9

 

S

 

4BYTE

EIS9

 

S/m

 

4BYTE

EIS9

 

kg/m

 

4BYTE

EIS9

 

C

 

4BYTE

EIS9

 

A

 

4BYTE

EIS9

 

A/m2

 

4BYTE

EIS9

 

Cm

 

4BYTE

EIS9

 

C/m2

 

4BYTE

EIS9

 

V/m

 

4BYTE

EIS9

 

C

 

4BYTE

EIS9

 

C/m2

 

4BYTE

EIS9

 

C/m2

 

4BYTE

EIS9

 

V

 

4BYTE

EIS9

 

V

 

4BYTE

EIS9

 

Am

 

4BYTE

EIS9

 

V

 

4BYTE

EIS9

 

J

 

4BYTE

EIS9

 

N

 

4BYTE

EIS9

 

1/s

 

4BYTE

EIS9

 

rad/s

 

4BYTE

EIS9

 

J/K

 

4BYTE

EIS9

 

W

 

4BYTE

EIS9

 

J

 

4BYTE

EIS9

 

Ohm

 

4BYTE

EIS9

 

m

 

4BYTE

EIS9

 

J

 

4BYTE

EIS9

 

cd/m2

 

4BYTE

EIS9

 

lm

 

4BYTE

EIS9

 

cd

 

4BYTE

EIS9

 

A/m

 

4BYTE

EIS9

 

Wb

 

4BYTE

EIS9

 

T

 

4BYTE

EIS9

 

Am

 

4BYTE

EIS9

 

T

 

4BYTE

EIS9

 

A/m

 

4BYTE

EIS9

 

A

 

4BYTE

EIS9

 

kg

 

4BYTE

EIS9

 

kg/s

 

4BYTE

EIS9

 

N/s

 

4BYTE

EIS9

 

rad

 

4BYTE

EIS9

 

°

 

4BYTE

EIS9

 

W

 

4BYTE

EIS9

 

 

 

4BYTE

EIS9

 

Pa

 

4BYTE

EIS9

 

Ohm

 

4BYTE

EIS9

 

Ohm

 

4BYTE

EIS9

 

Ohm m

 

4BYTE

EIS9

 

H

 

4BYTE

EIS9

 

sr

 

4BYTE

EIS9

 

W/m2

 

4BYTE

EIS9

 

m/s

 

4BYTE

EIS9

 

Pa

 

4BYTE

EIS9

 

N/m

 

4BYTE

EIS9

 

°C

 

4BYTE

EIS9

 

K

 

4BYTE

EIS9

 

J/K

 

4BYTE

EIS9

 

W/mK

 

4BYTE

EIS9

 

V/K

 

4BYTE

EIS9

 

s

 

4BYTE

EIS9

 

Nm

 

4BYTE

EIS9

 

m3

 

4BYTE

EIS9

 

m3/s

 

4BYTE

EIS9

 

N

 

4BYTE

EIS9

 

J

 

2BYTE

EIS10

U

 

16-Bit unsigned

2BYTE

EIS10

S

 

16-Bit signed

4BYTE

EIS11

U

 

32-Bit unsigned

4BYTE

EIS11

S

 

32-Bit signed

4BYTE

EIS12

 

 

Access control

1BYTE

EIS13

 

 

ASCII Character

1BYTE

EIS14

 

 

ASCII Character

14BYTE

EIS15

 

 

14 * EIS13

10BYTE

EIS15

 

 

10 * EIS13 (unofficial Type)

14BYTE

EIS15

 

 

14 * EIS13 as BYTE ARRAY (VT_UI1

8BYTE

EIS29

 

Wh

data type for power meter

8BYTE

EIS29

 

VARh

data type for power meter

 

Table 4.3.: Canonical Data types

Data size

EIS Type

(S)igned /
(U)nsigned

Unit

Description

4BYTE

UI4

 

 

Unsigned Integer

3BYTE

UI4

 

 

Unsigned Integer only 3 of 4 bytes used

8BYTE

UI8

 

 

Unsigned Integer

(warning) If you want to use one of these data types in a telegram, all indicated data type attributes must be entered in the telegram definition table:


Examples:
Correct:Incorrect:
;2BYTE;EIS10;U;; ;2BYTE;EIS10;;; here the "Signed/Unsigned" attribute is missing
;1BIT;EIS1;;;;1BIT;EIS1;;°C;
EIS 1 does not hold any units